State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Americaring Hands, LLC

419 Wolverley Lane, Allen, TX 75002 · Collin County · 9 licensed beds

HHSC licence number 312053 · licensed through August 14, 2027 · first licensed August 2024

The licence

Licensed by HHSC · Assisted Living Facility, Type B · Limited Liability Company (LLC)

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
16
Citations on file
Since September 2021
4
HHSC visits
1 routine inspection
13
Life safety and building
Life safety · physical plant · emergency

Position within Texas

16 citations — more than 94% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Americaring Hands, LLC

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility16Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility16
Median facility in Texas2

Visit history

Citations at each HHSC visit
112024-0122024-0432026-08
Citations at each HHSC visit
VisitTypeCitations
January 22, 2024life safety code inspection11
April 15, 2024life safety code inspection2
August 4, 2026health inspection3
August 4, 2026comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Physical plant 6
  • Life safety 6
  • Staffing and training 2
  • Resident care 1
  • Other 1
Citations by category
CategoryCitations
Physical plant6
Life safety6
Staffing and training2
Resident care1
Emergency management1

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

August 4, 2026 — comprehensive inspection, nothing cited

April 15, 2024 — life safety code inspection, 2 citations

January 22, 2024 — life safety code inspection, 11 citations

Citations from the life safety code inspection on January 22, 2024
What HHSC foundCorrected
Facility failed to provide one of the listed fire sprinkler systems according to the requirements of 32.2.3.5 in NFPA 101 Chapter 32.April 15, 2024
The facility failed to provide the minimum levels of illumination required in the facility.April 15, 2024
The facility failed to protect the attic according to the referenced codes and standards.April 15, 2024
The facility failed to ensure resident room doors would latch in their frames.April 15, 2024
The facility failed to ensure a working fireplace was only used in a building protected by fire sprinklers, was not located in a resident sleeping room, was only used in a room with carbon monoxide detection and had safety features to prevent residents from harm.April 15, 2024
The facility failed to ensure a bedroom had a floor area of at least 100 square feet for a single-occupancy bedroom or at least 80 square feet per resident in bedrooms occupied by more than one resident.April 15, 2024
The facility failed to ensure the building structure was sheathed to provide a 20-minute fire resistance rating or was constructed to meet the construction requirements for a nursing home.April 15, 2024
The facility failed to ensure the building electrical system met the references codes and standards.April 15, 2024
The facility failed to have a program to inspect, test, and maintain the fire alarm system and keep records of inspection, testing, and maintenance of the fire alarm system.April 15, 2024
The facility failed to provide hot water with a temperature between 100 and 120 degrees F for lavatories and bathing units.April 15, 2024
The facility failed to provide a telephone for use by residents and staff with emergency telephone numbers posted at or near the telephone.April 15, 2024

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.