State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Extended Senior Care And Services LLC

101 S Woodsway St W, Conroe, TX 77301 · Montgomery County · 12 licensed beds

HHSC licence number 307717 · licensed through February 6, 2029 · first licensed February 2020

The licence

Licensed by HHSC · Assisted Living Facility, Type B · Limited Liability Company (LLC)

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
22
Citations on file
Since September 2021
2
HHSC visits
1 routine inspection
22
Life safety and building
Life safety · physical plant · emergency

Position within Texas

22 citations — more than 97% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Extended Senior Care And Services LLC

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility22Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility22
Median facility in Texas2

Visit history

Citations at each HHSC visit
222026-05
Citations at each HHSC visit
VisitTypeCitations
May 7, 2026life safety code inspection22
May 7, 2026comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 13
  • Emergency management 5
  • Physical plant 4
Citations by category
CategoryCitations
Life safety13
Emergency management5
Physical plant4

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

May 7, 2026 — life safety code inspection, 22 citations

Citations from the life safety code inspection on May 7, 2026
What HHSC foundCorrected
The facility failed to ensure an attic was not used for storage.—
The facility failed to check gas heating systems prior to the heating season and to maintain records of the those checks.—
The facility failed to provide the minimum levels of illumination required in the facility.—
The facility failed to inspect, test, and maintain fire sprinkler system components.—
The facility failed to ensure the sensitivity of smoke detectors was checked according to NFPA 72.—
The facility failed to ensure resident room doors would latch in their frames.—
The facility failed to include a section addressing transportation in the emergency preparedness and response plan.—
The facility failed to ensure doors in the facility met the referenced codes and standards.—
The facility failed to review the plan at least annually to reflect changes in information, within 30 days following a disaster, within 30 days after a drill, and within 30 days after a change in rule or policy.—
The facility failed to have a complete fire safety plan for the protection of everyone in the facility in the event of a fire.—
The facility failed to provide portable fire extinguishers that met the referenced codes and standards.—
The facility failed to have and enforce a smoking policy.—
The facility failed to have a program to inspect, test, and maintain the fire sprinkler system and keep records of inspection, testing, and maintenance of the fire sprinkler system.—
The facility failed to provide the required emergency preparedness and response plan training and conduct drills.—
The facility failed to include a section addressing sheltering arrangements in the emergency preparedness and response plan.—
The failed to report fires timely via email or telephone and file the required written fire report.—
The facility failed to inspect, test, and maintain fire alarm system components.—
The facility failed to provide hot water with a temperature between 100 and 120 degrees F for lavatories and bathing units.—
The facility failed to conduct required fire drills and document fire drills on the required form.—
The facility failed to protect commercial cooking equipment according to the standard for ventilation control and fire protection of commercial cooking operations.—
The facility failed to provide a fire sprinkler system that met the referenced codes and standards.—
The facility failed to include a section addressing evacuation in the emergency preparedness and response plan.—

May 7, 2026 — comprehensive inspection, nothing cited

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.