State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Abri Homes

4240 Glenaire Drive, Dallas, TX 75229 · Dallas County · 5 licensed beds

HHSC licence number 311653 · licensed through August 14, 2028 · first licensed October 2023

The licence

Licensed by HHSC · Assisted Living Facility, Type B · Limited Liability Company (LLC)

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
13
Citations on file
Since September 2021
2
HHSC visits
1 routine inspection
13
Life safety and building
Life safety · physical plant · emergency

Position within Texas

13 citations — more than 91% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Abri Homes

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility13Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility13
Median facility in Texas2

Visit history

Citations at each HHSC visit
132023-1102025-08
Citations at each HHSC visit
VisitTypeCitations
November 13, 2023life safety code inspection13
August 14, 2025comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 10
  • Physical plant 3
Citations by category
CategoryCitations
Life safety10
Physical plant3

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

August 14, 2025 — comprehensive inspection, nothing cited

November 13, 2023 — life safety code inspection, 13 citations

Citations from the life safety code inspection on November 13, 2023
What HHSC foundCorrected
Facility failed to provide one of the listed fire sprinkler systems according to the requirements of 32.2.3.5 in NFPA 101 Chapter 32.April 1, 2024
The facility failed to check gas heating systems prior to the heating season and to maintain records of the those checks.April 1, 2024
The facility failed to ensure means of escape met the referenced codes and standards.April 1, 2024
The facility failed to provide protection where an exterior grade makes an abrupt change in level.April 1, 2024
The facility failed to keep buildings clean and free of hazards.April 1, 2024
The facility failed to ensure a working fireplace was only used in a building protected by fire sprinklers, was not located in a resident sleeping room, was only used in a room with carbon monoxide detection and had safety features to prevent residents from harm.April 1, 2024
The facility failed to ensure the building structure was sheathed to provide a 20-minute fire resistance rating or was constructed to meet the construction requirements for a nursing home.April 1, 2024
The facility failed to ensure the building electrical system met the references codes and standards.April 1, 2024
The facility failed to obtain pressure tests of gas piping in the facility.April 1, 2024
The facility failed to provide hot water with a temperature between 100 and 120 degrees F for lavatories and bathing units.April 1, 2024
The facility failed to have an ongoing and effective pest control program and to provide insect screens on operable windows.April 1, 2024
The facility failed to ensure equipment using natural gas or propane met the referenced codes and standards.April 1, 2024
The facility failed to ensure the power source for a fire alarm was a dedicated circuit in the facility's electrical system and that the fire alarm had a secondary, emergency power source.April 1, 2024

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.