State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Freemans Assisted Living LLC

500 Creektree Drive, Desoto, TX 75115 · Dallas County · 16 licensed beds

HHSC licence number 147248 · licensed through March 1, 2028 · first licensed February 2013

The licence

Licensed by HHSC · Assisted Living Facility, Type A · Limited Liability Company (LLC)

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
12
Citations on file
Since September 2021
4
HHSC visits
1 routine inspection
9
Life safety and building
Life safety · physical plant · emergency

Position within Texas

12 citations — more than 89% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Freemans Assisted Living LLC

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility12Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility12
Median facility in Texas2

Visit history

Citations at each HHSC visit
102022-0312022-0612025-06
Citations at each HHSC visit
VisitTypeCitations
March 2, 2022life safety code inspection10
June 6, 2022life safety code inspection1
June 25, 2025health inspection1
June 25, 2025comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 6
  • Emergency management 3
  • Records and administration 3
Citations by category
CategoryCitations
Life safety6
Emergency management3
Records and administration3

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

June 25, 2025 — health inspection, 1 citation

Citations from the health inspection on June 25, 2025
What HHSC foundCorrected
The facility failed to comply with the specific requirements for its licensure type.—

June 25, 2025 — comprehensive inspection, nothing cited

June 6, 2022 — life safety code inspection, 1 citation

Citations from the life safety code inspection on June 6, 2022
What HHSC foundCorrected
The provider failed to post the facility license as required.July 27, 2022

March 2, 2022 — life safety code inspection, 10 citations

Citations from the life safety code inspection on March 2, 2022
What HHSC foundCorrected
The facility failed to ensure means of escape met the referenced codes and standards.March 3, 2022
The facility's plan failed to include a process that ensures communication with the EMC.March 3, 2022
The facility failed to ensure the sensitivity of smoke detectors was checked according to NFPA 72.March 3, 2022
The facility failed to review the plan at least annually to reflect changes in information, within 30 days following a disaster, within 30 days after a drill, and within 30 days after a change in rule or policy.March 10, 2022
The facility failed to include a section addressing direction and control in the emergency preparedness and response plan.March 10, 2022
The facility failed to ensure resident room doors in a building that does not have fire sprinklers were solid doors that were at least 1-3/4 inches thick or had an opening protection rating of at least 20 minutes, that the doors were self-closing or automatic-closing, and that the doors would latch in their frames.May 21, 2022
The facility failed to provide the required emergency preparedness and response plan training and conduct drills.March 10, 2022
The facility failed to have a program to inspect, test, and maintain the fire alarm system and keep records of inspection, testing, and maintenance of the fire alarm system.March 3, 2022
The facility failed to store oxygen provided by the facility in a safe and sanitary manner.May 15, 2022
The facility's plan failed to document the contact information for the EMC for the area.March 3, 2022

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.