State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

CNS - Lakeway

2407 Lakeway Drive, Friendswood, TX 77546 · Galveston County · 6 licensed beds

HHSC licence number 308491 · licensed through February 3, 2028 · first licensed February 2022

The licence

Licensed by HHSC · Assisted Living Facility, Type B · Limited Liability Company (LLC)

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
17
Citations on file
Since September 2021
3
HHSC visits
1 routine inspection
15
Life safety and building
Life safety · physical plant · emergency

Position within Texas

17 citations — more than 94% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about CNS - Lakeway

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility17Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility17
Median facility in Texas2

Visit history

Citations at each HHSC visit
152022-0522025-02
Citations at each HHSC visit
VisitTypeCitations
May 5, 2022life safety code inspection15
February 6, 2025health inspection2
February 6, 2025comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 8
  • Physical plant 4
  • Emergency management 3
  • Staffing and training 1
  • Other 1
Citations by category
CategoryCitations
Life safety8
Physical plant4
Emergency management3
Staffing and training1
Records and administration1

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

February 6, 2025 — comprehensive inspection, nothing cited

May 5, 2022 — life safety code inspection, 15 citations

Citations from the life safety code inspection on May 5, 2022
What HHSC foundCorrected
Facility failed to provide one of the listed fire sprinkler systems according to the requirements of 32.2.3.5 in NFPA 101 Chapter 32.April 9, 2022
The facility failed to keep documentation about the fire sprinkler system onsite at the facility.March 11, 2022
The facility failed to ensure an attic was not used for storage.March 11, 2022
The facility failed to check gas heating systems prior to the heating season and to maintain records of the those checks.March 31, 2022
The facility failed to conduct and document a risk assessment for potential emergencies or disasters.April 6, 2022
The facility failed to ensure that interior wall and ceiling finishes met required surface burning characteristics.March 11, 2022
The facility failed to provide water drainage away from structures to prevent ponding or standing water at or near a building.March 25, 2022
The facility failed to inspect, test, and maintain fire sprinkler system components.May 6, 2022
The facility failed to maintain electrical, heating, and cooling systems so they worked safely.March 31, 2022
The facility failed to keep buildings clean and free of hazards.March 11, 2022
The facility failed to review the plan at least annually to reflect changes in information, within 30 days following a disaster, within 30 days after a drill, and within 30 days after a change in rule or policy.April 9, 2022
The facility failed to provide the required emergency preparedness and response plan training and conduct drills.April 9, 2022
The facility failed to ensure the building electrical system met the references codes and standards.March 11, 2022
The facility failed to provide smoke detectors in the required locations.March 11, 2022
The facility failed to ensure the power source for a fire alarm was a dedicated circuit in the facility's electrical system and that the fire alarm had a secondary, emergency power source.March 11, 2022

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.