State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Nixon Assisted Living Too

10222 Allwood St, Houston, TX 77016 · Harris County · 14 licensed beds

HHSC licence number 146179 · licensed through February 15, 2029 · first licensed November 2007

The licence

Licensed by HHSC · Assisted Living Facility, Type A · Limited Liability Company (LLC)

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
18
Citations on file
Since September 2021
3
HHSC visits
1 routine inspection
17
Life safety and building
Life safety · physical plant · emergency

Position within Texas

18 citations — more than 95% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Nixon Assisted Living Too

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility18Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility18
Median facility in Texas2

Visit history

Citations at each HHSC visit
172023-0412023-0602025-06
Citations at each HHSC visit
VisitTypeCitations
April 27, 2023life safety code inspection17
June 30, 2023life safety code inspection1
June 19, 2025comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 9
  • Physical plant 5
  • Emergency management 3
  • Records and administration 1
Citations by category
CategoryCitations
Life safety9
Physical plant5
Emergency management3
Records and administration1

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

June 19, 2025 — comprehensive inspection, nothing cited

June 30, 2023 — life safety code inspection, 1 citation

April 27, 2023 — life safety code inspection, 17 citations

Citations from the life safety code inspection on April 27, 2023
What HHSC foundCorrected
The facility failed to keep documentation about the fire alarm system onsite at the facility.August 9, 2023
The facility failed to ensure the total area of all windows in a bedroom was at least 8% of the minimum required bedroom floor area.June 9, 2023
The facility failed to provide water drainage away from structures to prevent ponding or standing water at or near a building.August 9, 2023
The facility failed to provide the minimum levels of illumination required in the facility.August 9, 2023
The facility failed to ensure escape routes through living rooms and dining rooms were kept clear of obstructions.June 9, 2023
The facility failed to train staff in the use of fire extinguishers, failed to inspect and maintain fire extinguishers, and failed to keep records of inspection and maintenance of fire extinguishers.June 9, 2023
The facility failed to ensure doors in the facility met the referenced codes and standards.August 9, 2023
The facility failed to review the plan at least annually to reflect changes in information, within 30 days following a disaster, within 30 days after a drill, and within 30 days after a change in rule or policy.August 9, 2023
The facility failed to obtain documentation from the local Authorities Having Jurisdiction (AHJ) that show that the facility meets local requirements.August 9, 2023
The facility failed to include a section addressing direction and control in the emergency preparedness and response plan.August 9, 2023
The facility failed to ensure resident room doors in a building that does not have fire sprinklers were solid doors that were at least 1-3/4 inches thick or had an opening protection rating of at least 20 minutes, that the doors were self-closing or automatic-closing, and that the doors would latch in their frames.August 9, 2023
The facility failed to provide the required emergency preparedness and response plan training and conduct drills.August 9, 2023
The facility failed to inspect, test, and maintain fire alarm system components.August 9, 2023
The facility failed to provide hot water with a temperature between 100 and 120 degrees F for lavatories and bathing units.June 9, 2023
The facility failed to conduct required fire drills and document fire drills on the required form.June 9, 2023
The facility failed to ensure that there was at least one operable window in every bedroom, that the operable window opened to the outside, that the sill of the operable window was within 44 inches of the floor, and that the window could be opened from the inside by all residents who occupy the bedroom, without tools or special devices.June 9, 2023
The facility failed to protect commercial cooking equipment according to the standard for ventilation control and fire protection of commercial cooking operations.August 9, 2023

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.