State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Atascocita Seniors Care Home, Inc

18007 Landing Brook Dr, Humble, TX 77346 · Harris County · 8 licensed beds

HHSC licence number 311829 · licensed through January 1, 2027 · first licensed January 2001

The licence

Licensed by HHSC · Assisted Living Facility, Type B · FOR-PROFIT CORPORATION

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
19
Citations on file
Since September 2021
2
HHSC visits
1 routine inspection
18
Life safety and building
Life safety · physical plant · emergency

Position within Texas

19 citations — more than 96% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Atascocita Seniors Care Home, Inc

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility19Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility19
Median facility in Texas2

Visit history

Citations at each HHSC visit
192024-0602024-09
Citations at each HHSC visit
VisitTypeCitations
June 12, 2024life safety code inspection19
September 24, 2024comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Physical plant 7
  • Emergency management 6
  • Life safety 5
  • Records and administration 1
Citations by category
CategoryCitations
Physical plant7
Emergency management6
Life safety5
Records and administration1

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

September 24, 2024 — comprehensive inspection, nothing cited

June 12, 2024 — life safety code inspection, 19 citations

Citations from the life safety code inspection on June 12, 2024
What HHSC foundCorrected
The facility failed to ensure an attic was not used for storage.June 12, 2024
The facility failed to check gas heating systems prior to the heating season and to maintain records of the those checks.August 1, 2024
The facility failed to conduct and document a risk assessment for potential emergencies or disasters.August 1, 2024
The facility failed to provide water drainage away from structures to prevent ponding or standing water at or near a building.August 1, 2024
The facility failed to provide the minimum levels of illumination required in the facility.August 1, 2024
The facility failed to ensure the sensitivity of smoke detectors was checked according to NFPA 72.August 1, 2024
The facility failed to provide a dining area in proportion to the licensed capacity of the facility with exterior windows that provide a view to the outside that is accessible from resident living units or bedrooms via an indoor or covered path.August 1, 2024
The facility failed to include a section addressing transportation in the emergency preparedness and response plan.August 1, 2024
The facility failed to ensure doors in the facility met the referenced codes and standards.June 12, 2024
The facility failed to keep buildings clean and free of hazards.August 1, 2024
The facility failed to review the plan at least annually to reflect changes in information, within 30 days following a disaster, within 30 days after a drill, and within 30 days after a change in rule or policy.August 1, 2024
The facility failed to obtain documentation from the local Authorities Having Jurisdiction (AHJ) that show that the facility meets local requirements.August 1, 2024
The facility failed to ensure a bedroom had a floor area of at least 100 square feet for a single-occupancy bedroom or at least 80 square feet per resident in bedrooms occupied by more than one resident.August 1, 2024
The facility failed to provide the required emergency preparedness and response plan training and conduct drills.August 1, 2024
The facility failed to include a section addressing sheltering arrangements in the emergency preparedness and response plan.August 1, 2024
The facility failed to inspect, test, and maintain fire alarm system components.August 1, 2024
The facility failed to provide hot water with a temperature between 100 and 120 degrees F for lavatories and bathing units.June 12, 2024
The facility failed to conduct required fire drills and document fire drills on the required form.August 1, 2024
The facility failed to include a section addressing evacuation in the emergency preparedness and response plan.August 1, 2024

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.