State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Wyndham Court of Plano

3000 Midway Rd, Plano, TX 75093 · Collin County · 88 licensed beds

HHSC licence number 311804 · licensed through November 21, 2029 · first licensed September 2000

The licence

Licensed by HHSC · Assisted Living Facility, Type B · Limited Liability Company (LLC) · managed by Silvercare Management LLC

Certifications and programs, as listed by HHSC
Alzheimer's certification
Yes, through 11/21/2029
Alzheimer's unit capacity
78
Accepts Medicaid
No
14
Citations on file
Since September 2021
2
HHSC visits
1 routine inspection
14
Life safety and building
Life safety · physical plant · emergency

Position within Texas

14 citations — more than 92% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Wyndham Court of Plano

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility14Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility14
Median facility in Texas2

Visit history

Citations at each HHSC visit
142024-0602026-04
Citations at each HHSC visit
VisitTypeCitations
June 6, 2024life safety code inspection14
April 2, 2026comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 10
  • Physical plant 4
Citations by category
CategoryCitations
Life safety10
Physical plant4

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

April 2, 2026 — comprehensive inspection, nothing cited

June 6, 2024 — life safety code inspection, 14 citations

Citations from the life safety code inspection on June 6, 2024
What HHSC foundCorrected
The facility failed to provide smoke compartmentation where required.November 7, 2024
The facility failed to provide an approved outdoor area for the segregated unit.November 7, 2024
The facility failed to ensure portable fire extinguishers were mounted on hangers or brackets supplied with the fire extinguisher or mounted in a fire extinguisher cabinet, were protected from impact or dislodgement, and were mounted at the appropriate height based on the weight of the extinguisher.July 21, 2024
The facility failed to test and maintain an emergency generator that provides power to emergency lighting.July 21, 2024
The facility failed to provide the minimum levels of illumination required in the facility.July 21, 2024
The facility failed to ensure the building electrical system met the referenced codes and standards.July 21, 2024
The facility failed to ensure means of egress met the referenced codes and standards.November 7, 2024
The facility failed to ensure doors in the facility met the referenced codes and standards.July 21, 2024
The facility failed to provide portable fire extinguishers that met the referenced codes and standards.July 21, 2024
The facility failed to provide proper locking devicesJuly 21, 2024
The facility failed to ensure flammable and combustible liquids were not stored in buildings used by residents.July 21, 2024
The facility failed to provide smoke detectors in the required locations.July 21, 2024
The facility failed to notify HHSC in writing prior to the start of building rehabilitation.July 21, 2024
The facility failed to provide a fire alarm control panel visible to facility staff or monitored by devices carried by facility staff, that indicated the location of a fire alarm event.July 21, 2024

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.