State assisted-living licensing record · Texas HHSC · record as pulled September 11, 2026· Not the federal nursing home survey

Ihcs Residential, INC.

15218 Pebble Forest Dr, San Antonio, TX 78232 · Bexar County · 9 licensed beds

HHSC licence number 147993 · licensed, enforcement action pending through October 16, 2028 · first licensed April 2003

The licence

Licensed by HHSC · Assisted Living Facility, Type A · FOR-PROFIT CORPORATION

Certifications and programs, as listed by HHSC
Alzheimer's certification
No
Accepts Medicaid
No
16
Citations on file
Since September 2021
2
HHSC visits
1 routine inspection
14
Life safety and building
Life safety · physical plant · emergency

Position within Texas

16 citations — more than 94% of the 1,995 licensed assisted living facilities in Texas. Compared only within Texas: a citation from HHSC means what it means in Texas, and there is no national assisted living record to compare to. Counted over 5 years, which holds two or three routine inspections. How this is calculated

Not in this record

Scope and severity, and enforcement. HHSC rates each finding on a scope-and-severity scale but does not publish the rating per facility, and it records fines and enforcement actions separately; neither is republished here. What is here is unusual among states: HHSC inspects fire and life safety itself and publishes those findings per facility, so this record carries a real life safety section.

Get an email about Ihcs Residential, INC.

One email when it happens, from the HHSC record as it is pulled each month. No account; stop it any time with one click.

Which alerts

This is the state licensing record, not the federal nursing home survey. Your address is used for these alerts and nothing else.

Life safety and building citations

The citations about the building itself — fire and life safety, physical plant and emergency management. Usually the maintenance side’s to fix.

How that compares

Citations on file over 5 years

Compared with the median licensed assisted living facility in Texas. Within-state only.

This facility16Texas median2
Citations on file over 5 years, compared
MeasureCitations
This facility16
Median facility in Texas2

Visit history

Citations at each HHSC visit
162025-1202026-06
Citations at each HHSC visit
VisitTypeCitations
December 31, 2025life safety code inspection16
June 16, 2026comprehensive inspection0

What the citations cover

Citations by category (TagProof's grouping)
  • Life safety 8
  • Emergency management 5
  • Records and administration 2
  • Physical plant 1
Citations by category
CategoryCitations
Life safety8
Emergency management5
Records and administration2
Physical plant1

Every visit on file since September 2021

As published by HHSC, newest first, including visits that cited nothing. The wording is HHSC’s own.

June 16, 2026 — comprehensive inspection, nothing cited

December 31, 2025 — life safety code inspection, 16 citations

Citations from the life safety code inspection on December 31, 2025
What HHSC foundCorrected
The facility failed to check gas heating systems prior to the heating season and to maintain records of the those checks.—
The facility failed to conduct and document a risk assessment for potential emergencies or disasters.—
The facility failed to ensure the sensitivity of smoke detectors was checked according to NFPA 72.—
The facility failed to ensure the building electrical system met the referenced codes and standards.—
The facility failed to include a section addressing transportation in the emergency preparedness and response plan.—
The facility failed to develop and maintain a written emergency preparedness and response plan based on its risk assessment under subsection (b) of this section and that is adequate to protect facility residents and staff in a disaster or emergency.—
The facility failed to have and enforce a smoking policy.—
The facility failed to provide the required emergency preparedness and response plan training and conduct drills.—
The facility failed to have a program to inspect, test, and maintain the fire alarm system and keep records of inspection, testing, and maintenance of the fire alarm system.—
The facility failed to ensure flammable and combustible liquids were not stored in buildings used by residents.—
The facility failed to notify the EMC of the facility's plan, take actions to coordinate with the EMC, and document communications with the EMC.—
The facility failed to obtain pressure tests of gas piping in the facility.—
The facility failed to store oxygen provided by the facility in a safe and sanitary manner.—
The facility's plan failed to document the contact information for the EMC for the area.—
The facility failed to include a section addressing evacuation in the emergency preparedness and response plan.—
The facility failed to correct a site or building condition that was a fire, health, or physical hazard.—

Reflects the HHSC record as pulled September 11, 2026. A recent visit may not appear yet. This is the Texas state licensing record; it is not the federal nursing home survey and the two are never combined.