Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

KELLER LANDING

TUSCUMBIA, AL · 109 certified beds · Last Life Safety survey February 24, 2022

CMS Certification Number 015028 · first certified July 1977

Ownership

Operated by GENESIS HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

11
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
1
Tags cited more than once
Across separate surveys
6
Inspection & testing records
Of the citations on file

Position within AL

11 citations — more than 58% of the 224 certified nursing homes in AL. Compared within AL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 2 citations; the earlier surveys in the window averaged 4.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (March 2023 to July 2023), and past the point by which nine in ten US facilities have been surveyed. This facility’s last Life Safety survey was February 2022. Nursing homes nationally are typically surveyed 12–17 months after the last one (median 14), measured over 19,385 consecutive surveys in the last two years of CMS records. AL has too few recent surveys to measure on its own, so the national interval is used.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about KELLER LANDING

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 11 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in AL, and nationally. Surveyors differ markedly between states, so the AL figure is the meaningful one.

This facility11AL median9National median11
Citations on file over three years, compared
MeasureCitations
This facility11
Median facility in AL9
Median facility nationally11

Survey history

Citations at each Life Safety survey
62018-0932019-0622022-02
Citations at each Life Safety survey
Survey dateCitations
September 13, 20186
June 20, 20193
February 24, 20222

Most-cited tags

Most-cited tags at this facility
K-05213K-02321K-02931K-03001K-03251K-03531K-03721K-09141
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.32022-02-24
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.12022-02-24
K-0293Have properly located and lighted "Exit" signs.12018-09-13
K-0300Meet other general requirements that are deficient.12019-06-20
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.12019-06-20
K-0353Inspect, test, and maintain automatic sprinkler systems.12018-09-13
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12018-09-13
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.12018-09-13

What the citations cover

Citations by CMS category
  • Egress Deficiencies 4
  • Services Deficiencies 3
  • Smoke Deficiencies 3
  • Gas, Vacuum, and Electrical Systems Deficiencies 1
Citations by CMS category
CategoryCitations
Egress Deficiencies4
Services Deficiencies3
Smoke Deficiencies3
Gas, Vacuum, and Electrical Systems Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 24, 2022 — 2 citations

Citations issued on February 24, 2022
TagWhat the surveyor checksStatus
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (March 29, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 15, 2022)

June 20, 2019 — 3 citations

Citations issued on June 20, 2019
TagWhat the surveyor checksStatus
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (July 19, 2019)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (July 19, 2019)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (July 19, 2019)

September 13, 2018 — 6 citations

Citations issued on September 13, 2018
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 27, 2018)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (September 27, 2018)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 27, 2018)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 27, 2018)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (September 27, 2018)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 27, 2018)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.