Citation tags
Surveyors record findings as numbered tags. Nursing homes receive two sets, published together but drawn from different rules: K-tags come from the Life Safety Code, and E-tags from the Emergency Preparedness requirements at 42 CFR §483.73.
Life Safety Code — 120 tags
| Tag | What the surveyor checks | Facilities | Cited twice or more |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 9,765 | 5,024 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 7,559 | 3,049 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 6,470 | 2,197 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 6,068 | 1,925 |
| K-0363 | Install corridor and hallway doors that block smoke. | 6,055 | 2,198 |
| K-0324 | Provide properly protected cooking facilities. | 5,843 | 1,560 |
| K-0712 | Have simulated fire drills held at unexpected times. | 5,637 | 2,044 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 5,344 | 1,857 |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | 4,576 | 1,181 |
| K-0923 | Have proper medical gas storage and administration areas. | 4,257 | 829 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 4,249 | 1,261 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 4,129 | 907 |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 4,107 | 962 |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 3,804 | 791 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 3,757 | 822 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 3,272 | 596 |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 3,231 | 941 |
| K-0351 | Install an approved automatic sprinkler system. | 3,141 | 568 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 3,029 | 649 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2,660 | 416 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 2,586 | 467 |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | 2,538 | 365 |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | 1,987 | 318 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 1,758 | 343 |
| K-0161 | Use approved construction type or materials. | 1,719 | 399 |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | 1,546 | 123 |
| K-0711 | Provide a written emergency evacuation plan. | 1,545 | 204 |
| K-0271 | Have exits that are accessible at all times. | 1,339 | 153 |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | 1,299 | 135 |
| K-0781 | Have restrictions on the use of portable space heaters. | 1,142 | 77 |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | 1,023 | 126 |
| K-0281 | Install proper backup exit lighting. | 949 | 104 |
| K-0311 | Have an enclosure around a vertical opening shaft. | 937 | 191 |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | 928 | 105 |
| K-0919 | Meet requirements for the use of electrical equipment. | 924 | 194 |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | 894 | 71 |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | 893 | 124 |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | 888 | 144 |
| K-0100 | Meet other general requirements. | 788 | 110 |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | 781 | 33 |
| K-0912 | Have power receptacles that are properly grounded. | 733 | 66 |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | 730 | 133 |
| K-0753 | Have restrictions on the use of highly flammable decorations. | 698 | 38 |
| K-0325 | Have properly installed hallway dispensers for alcohol-based hand rub. | 648 | 32 |
| K-0232 | Have corridors or aisles that are unobstructed and are at least 8 feet in width. | 560 | 55 |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | 550 | 49 |
| K-0500 | Meet other general requirements that are deficient. | 542 | 55 |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | 482 | 59 |
| K-0541 | Install properly constructed and protected linen or trash chutes. | 481 | 102 |
| K-0331 | Construct fire resistant interior walls. | 452 | 24 |
| K-0300 | Meet other general requirements that are deficient. | 398 | 55 |
| K-0343 | Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire. | 397 | 17 |
| K-0352 | Properly install and monitor supervisory attachments on automatic sprinkler systems. | 395 | 13 |
| K-0131 | Meet requirements for sections of health care facilities separated by fire resistive construction. | 384 | 42 |
| K-0929 | Ensure precautions for handling oxygen cylinders and equipment are correctly followed. | 362 | 26 |
| K-0927 | Have proper fire barriers, ventilation and signs for the transfilling of oxygen. | 351 | 34 |
| K-0915 | Have proper power supply for life support equipment. | 341 | 48 |
| K-0344 | Have an alternate power supply for its alarm system. | 329 | 29 |
| K-0200 | Meet other general requirements. | 296 | 11 |
| K-0901 | Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel. | 261 | 13 |
| K-0133 | Install a two-hour-resistant firewall separation. | 261 | 56 |
| K-0361 | Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected. | 243 | 10 |
| K-0754 | Provide properly sized and located linen or trash receptacles. | 237 | 23 |
| K-0522 | Have an externally vented heating system. | 213 | 8 |
| K-0922 | Meet requirements for the use and maintenance of medical gas equipment. | 196 | 21 |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. | 180 | 5 |
| K-0371 | Have properly sized and located compartments to protect residents from smoke. | 170 | 12 |
| K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. | 164 | 7 |
| K-0226 | Have horizontal exits used in accordance with safety requirements. | 156 | 9 |
| K-0751 | Have restrictions on the use of flammable curtains. | 136 | 4 |
| K-0364 | Install properly constructed windows in hallway walls or doors. | 118 | 1 |
| K-0908 | Ensure gas and vacuum systems are inspected and tested as part of a maintenance program. | 117 | 9 |
| K-0932 | Meet other general requirements. | 112 | 3 |
| K-0132 | Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction. | 108 | 11 |
| K-0925 | Ensure that sources of ignition are removed from patients receiving respiratory therapy. | 107 | 5 |
| K-0900 | Meet Health Care Facilities Code mechanical requirements. | 106 | 4 |
| K-0917 | Ensure electrical receptacles or cover plates have distinctive color or marking. | 105 | 1 |
| K-0227 | Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements. | 82 | 2 |
| K-0930 | Ensure proper storage of liquid oxygen. | 77 | 5 |
| K-0221 | Provide rooms that can be unlocked from inside without a key. | 75 | 0 |
| K-0907 | Ensure medical gas and vacuum systems have documented maintenance programs. | 73 | 4 |
| K-0241 | Have correct number of accessible exits for each story. | 56 | 25 |
| K-0913 | Ensure operating rooms are properly protected and written records are maintained and available for inspection. | 49 | 1 |
| K-0771 | Ensure that smoke control systems are tested and documented in accordance with established engineering principles. | 49 | 2 |
| K-0791 | Ensure that any exit in an area undergoing construction, repair, or improvements shall be inspected daily to ensure its ability to be used instantly in case of emergency. | 49 | 1 |
| K-0233 | Install resident room doors of proper design and width. | 48 | 7 |
| K-0252 | Provide at least two remote exits on each floor or fire section of the building. | 47 | 16 |
| K-0224 | Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion. | 44 | 1 |
| K-0163 | Install noncombustible or limited-combustible interior walls. | 43 | 3 |
| K-0928 | Ensure equipment listed for use in oxygen-enriched atmospheres are correctly labeled. | 40 | 0 |
| K-0902 | Meet requirements for the installation and maintenance of medical gas and medical vacuum systems. | 32 | 2 |
| K-0231 | Provide large enough exits. | 29 | 0 |
| K-0379 | Have proper openings in smoke barrier doors. | 28 | 0 |
| K-0909 | Ensure gas and vacuum piping is labeled. | 28 | 2 |
| K-0251 | Conform to length requirements for dead end corridors. | 26 | 1 |
| K-0255 | Ensure that suites are correctly sub-divided by noncombustible or limited-combustible construction. | 20 | 0 |
| K-0525 | Enure that solid fuel-burning fireplaces are not in patient sleeping areas. | 18 | 1 |
| K-0524 | Ensure that gas fire places are out of the reach of patients and can be shut off if unit is working improperly. | 17 | 1 |
| K-0906 | Ensure gas cylinders are properly stored. | 16 | 0 |
| K-0532 | Have a properly installed and maintained dumbwaiter or escalator. | 16 | 1 |
| K-0523 | Ensure that HVAC heat units are suspended and out of the reach of patients and can be shut off if unit is working improperly. | 16 | 0 |
| K-0400 | Meet fire sprinkler requirement for tall buildings. | 16 | 0 |
| K-0904 | Have a properly installed medical gas master alarm panel. | 14 | 0 |
| K-0373 | Have enough space near smoke barriers to protect residents. | 12 | 1 |
| K-0254 | Provide hallway or ground-level exits in all residents' rooms. | 12 | 2 |
| K-0905 | Ensure that gas containers are correctly designed and tested, and in locations that are labeled. | 11 | 0 |
| K-0924 | Ensure that anesthesia apparatus are tested after any adjustment, modification or repair. | 11 | 0 |
| K-0162 | Have a combustible roofing system that meets safety standards. | 10 | 0 |
| K-0261 | Have properly spaced exits within rooms. | 9 | 2 |
| K-0253 | Provide two separate exits in rooms of more than 1000 square feet. | 5 | 1 |
| K-0381 | Provide outside doors or windows in every resident room. | 4 | 0 |
| K-0112 | Add automatic sprinklers after major renovation. | 3 | 0 |
| K-0910 | Ensure when modifications are made that breach pipelines, testing is conducted on downstream portions of the piping system. | 2 | 0 |
| K-0752 | Ensure new upholstered furniture and mattresses meet char length and heat release criteria. | 2 | 0 |
| K-0322 | Ensure that laboratories employing quantities of flammable, combustible, or hazardous materials have fire resistant walls and automatic sprinkler system. | 1 | 0 |
| K-0038 | Exits that are accessible at all times. | 1 | 0 |
| K-0933 | Ensure that periodic evaluations are made of hazards that could be encountered during surgical procedures, and fire prevention procedures are established. | 1 | 0 |
| K-0130 | Have other fire safety features required by fire safety codes. | 1 | 0 |
| K-0025 | Walls that prevent smoke from passing through and would resist fire for at least one hour. | 1 | 0 |
| K-0072 | Exits that are free from obstructions and can be used at all times. | 1 | 0 |
Emergency Preparedness — 26 tags
Cited at roughly half of all cited facilities, and mostly about plans, training and records rather than the building itself. They have their own index: the Emergency Preparedness Index.
| Tag | What the surveyor checks | Facilities | Cited twice or more |
|---|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | 2,836 | 566 |
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | 2,051 | 237 |
| E-0041 | Implement emergency and standby power systems. | 1,413 | 232 |
| E-0015 | Address subsistence needs for staff and patients. | 1,272 | 192 |
| E-0037 | Establish staff and initial training requirements. | 1,269 | 188 |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | 1,104 | 92 |
| E-0030 | List the names and contact information of those in the facility. | 857 | 67 |
| E-0036 | Establish emergency prep training and testing. | 788 | 68 |
| E-0026 | Establish roles under a Waiver declared by secretary. | 738 | 54 |
| E-0013 | Develop Emergency Preparedness policies and procedures. | 673 | 44 |
| E-0031 | Provide emergency officials' contact information. | 642 | 47 |
| E-0007 | Address patient/client population and determine types of services needed. | 576 | 45 |
| E-0025 | Create arrangements with other facilities to receive patients. | 539 | 27 |
| E-0029 | Develop a communication plan. | 483 | 33 |
| E-0024 | Establish policies and procedures for volunteers. | 481 | 30 |
| E-0020 | Establish policies and procedures including evacuation. | 481 | 42 |
| E-0032 | Provide primary/alternate means for communication. | 466 | 35 |
| E-0035 | Provide family notifications of emergency plan. | 429 | 30 |
| E-0009 | Include a process for Emergency Preparedness collaboration. | 425 | 41 |
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | 420 | 23 |
| E-0023 | Establish policies and procedures for medical documentation. | 304 | 24 |
| E-0034 | Provide a means of sharing information on occupancy/needs. | 295 | 15 |
| E-0022 | Establish policies and procedures for sheltering. | 279 | 19 |
| E-0033 | Establish methods for sharing information. | 190 | 9 |
| E-0001 | Establish an Emergency Preparedness Program (EP). | 183 | 7 |
| E-0042 | Meet the requirements of an integrated health system. | 43 | 1 |