Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
DRIFTWOOD HEALTHCARE CENTER - HAYWARD
HAYWARD, CA · 88 certified beds · Last Life Safety survey August 9, 2024
CMS Certification Number 555533 · first certified December 1992
Ownership
Operated by MARINER HEALTH CARE · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within CA
39 citations — more than 96% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 6 citations; the earlier surveys in the window averaged 8.3. With 5 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Past the typical window (August 2025 to January 2026). Most CA facilities have been surveyed by January 2027. This facility’s last Life Safety survey was August 2024. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about DRIFTWOOD HEALTHCARE CENTER - HAYWARD
One email when it happens. No account; stop it any time with one click.
6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
6 of the 39 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 39 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 39 |
| Median facility in CA | 19 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| August 29, 2019 | 10 |
| September 2, 2022 | 20 |
| August 11, 2023 | 2 |
| August 6, 2024 | 1 |
| August 9, 2024 | 6 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0324 | Provide properly protected cooking facilities. | 3 | 2024-08-09 |
| K-0363 | Install corridor and hallway doors that block smoke. | 3 | 2024-08-09 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2024-08-09 |
| K-0711 | Provide a written emergency evacuation plan. | 2 | 2024-08-09 |
| K-0919 | Meet requirements for the use of electrical equipment. | 2 | 2024-08-06 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2024-08-09 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2022-09-02 |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | 2 | 2022-09-02 |
What the citations cover
- Smoke Deficiencies 18
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Emergency Preparedness Deficiencies 6
- Miscellaneous Deficiencies 4
- Other 5
| Category | Citations |
|---|---|
| Smoke Deficiencies | 18 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Emergency Preparedness Deficiencies | 6 |
| Miscellaneous Deficiencies | 4 |
| Egress Deficiencies | 2 |
| Services Deficiencies | 2 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
August 9, 2024 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (August 20, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 20, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 20, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 20, 2024) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (August 20, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 20, 2024) |
August 6, 2024 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (August 6, 2024) |
August 11, 2023 — 2 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 11, 2023) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (August 11, 2023) |
September 2, 2022 — 20 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (October 26, 2022) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (October 26, 2022) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (October 26, 2022) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (October 26, 2022) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (October 26, 2022) |
August 29, 2019 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (November 20, 2019) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (November 20, 2019) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.