Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Eagle Point Nursing and Rehabilitation

Clinton, IA · 75 certified beds · Last Life Safety survey April 23, 2026

CMS Certification Number 165218 · first certified April 1994

Ownership

Operated by SHLOMO HOFFMAN · For profit - Limited Liability company

  • Ownership changed July 1, 2023 (change of ownership)from OPCO CLINTON IA LLC
10
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
7
Inspection & testing records
Of the citations on file

Position within IA

10 citations — more than 34% of the 387 certified nursing homes in IA. Compared within IA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 4 citations; the earlier surveys in the window averaged 3. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 5 months from now. This facility’s last Life Safety survey was April 2026. Facilities in IA are typically surveyed 11–13 months after the last one (median 12), measured over 700 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Eagle Point Nursing and Rehabilitation

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 10 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in IA, and nationally. Surveyors differ markedly between states, so the IA figure is the meaningful one.

This facility10IA median12National median11
Citations on file over three years, compared
MeasureCitations
This facility10
Median facility in IA12
Median facility nationally11

Survey history

Citations at each Life Safety survey
42024-0622025-0442026-04
Citations at each Life Safety survey
Survey dateCitations
June 6, 20244
April 3, 20252
April 23, 20264

Most-cited tags

Most-cited tags at this facility
K-03452K-03532K-07121K-09201K-02111K-02911K-09211K-09181
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22026-04-23
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-04-03
K-0712Have simulated fire drills held at unexpected times.12024-06-06
K-0920Ensure proper usage of power strips and extension cords.12025-04-03
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.12024-06-06
K-0291Install emergency lighting that can last at least 1 1/2 hours.12026-04-23
K-0921Ensure that testing and maintenance of electrical equipment is performed.12026-04-23
K-0918Have generator or other power source capable of supplying service within 10 seconds.12026-04-23

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 4
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
  • Egress Deficiencies 2
  • Miscellaneous Deficiencies 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies4
Gas, Vacuum, and Electrical Systems Deficiencies3
Egress Deficiencies2
Miscellaneous Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 23, 2026 — 4 citations

Citations issued on April 23, 2026
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 5, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 4, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 6, 2026)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (May 22, 2026)

April 3, 2025 — 2 citations

Citations issued on April 3, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 16, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 16, 2025)

June 6, 2024 — 4 citations

Citations issued on June 6, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 20, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 20, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 20, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 20, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.