Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

APERION CARE KOKOMO

KOKOMO, IN · 105 certified beds · Last Life Safety survey August 15, 2025

CMS Certification Number 155064 · first certified February 1968

Ownership

Operated by APERION CARE · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

53
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within IN

53 citations — more than 100% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 23.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: July 2026 to October 2026. This facility’s last Life Safety survey was August 2025. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about APERION CARE KOKOMO

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

13 of the 53 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 53 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.

This facility53IN median15National median11
Citations on file over three years, compared
MeasureCitations
This facility53
Median facility in IN15
Median facility nationally11

Survey history

Citations at each Life Safety survey
282023-07192024-0962025-08
Citations at each Life Safety survey
Survey dateCitations
July 28, 202328
September 23, 202419
August 15, 20256

Most-cited tags

Most-cited tags at this facility
E-00413K-09183K-02222K-07112K-03452K-03212K-05112K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
E-0041Implement emergency and standby power systems.32025-08-15
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-08-15
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-08-15
K-0711Provide a written emergency evacuation plan.22024-09-23
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-08-15
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22024-09-23
K-0511Have properly installed electrical wiring and gas equipment.22024-09-23
K-0324Provide properly protected cooking facilities.22024-09-23

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 13
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Miscellaneous Deficiencies 8
  • Other 10
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies13
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies10
Miscellaneous Deficiencies8
Egress Deficiencies7
Services Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 15, 2025 — 6 citations

Citations issued on August 15, 2025
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (October 3, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 17, 2025)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (October 3, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 11, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 3, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (October 3, 2025)

September 23, 2024 — 19 citations

Citations issued on September 23, 2024
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (November 20, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has plan of correction (December 16, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (November 20, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (November 20, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 20, 2024)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (November 20, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 20, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 20, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 20, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 20, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (November 20, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 20, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has plan of correction (December 16, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 20, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 20, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 20, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 20, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 20, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 20, 2024)

July 28, 2023 — 28 citations

Citations issued on July 28, 2023
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (September 25, 2023)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (September 25, 2023)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (September 25, 2023)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (September 25, 2023)
E-0029Develop a communication plan.Deficient, Provider has date of correction (September 25, 2023)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (September 25, 2023)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (September 26, 2023)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (September 25, 2023)
K-0100Meet other general requirements.Deficient, Provider has date of correction (September 25, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 25, 2023)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (September 25, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 25, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 25, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 25, 2023)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (September 25, 2023)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 25, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 25, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 25, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 25, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (September 26, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 25, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 25, 2023)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (September 25, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (September 25, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 27, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 25, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 25, 2023)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (September 26, 2023)