Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

MEDICALODGES COFFEYVILLE ON MIDLAND

COFFEYVILLE, KS · 100 certified beds · Last Life Safety survey May 13, 2024

CMS Certification Number 175290 · first certified May 1994

Ownership

Operated by MEDICALODGES, INC. · For profit - Corporation

  • Ownership changed May 1, 2022 (change of ownership)from HEALTH MANAGEMENT OF KANSAS INC
45
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
15
Tags cited more than once
Across separate surveys
23
Inspection & testing records
Of the citations on file

Position within KS

45 citations — more than 92% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 16.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (January 2026 to March 2026), and past the point by which nine in ten KS facilities have been surveyed. This facility’s last Life Safety survey was May 2024. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about MEDICALODGES COFFEYVILLE ON MIDLAND

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 45 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 45 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility45KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility45
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
162020-02172022-07122024-05
Citations at each Life Safety survey
Survey dateCitations
February 26, 202016
July 14, 202217
May 13, 202412

Most-cited tags

Most-cited tags at this facility
K-03453K-07413K-03213K-03533K-09203K-07123K-09182K-02932
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32024-05-13
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32024-05-13
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32024-05-13
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-05-13
K-0920Ensure proper usage of power strips and extension cords.32024-05-13
K-0712Have simulated fire drills held at unexpected times.32024-05-13
K-0918Have generator or other power source capable of supplying service within 10 seconds.22022-07-14
K-0293Have properly located and lighted "Exit" signs.22022-07-14

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 19
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Miscellaneous Deficiencies 7
  • Egress Deficiencies 5
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies19
Gas, Vacuum, and Electrical Systems Deficiencies8
Miscellaneous Deficiencies7
Egress Deficiencies5
Emergency Preparedness Deficiencies4
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 13, 2024 — 12 citations

Citations issued on May 13, 2024
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 11, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 11, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 11, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 11, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 15, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 15, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 11, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 11, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 11, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (July 11, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 11, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 11, 2024)

July 14, 2022 — 17 citations

Citations issued on July 14, 2022
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (July 8, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 8, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 8, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 8, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 8, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 8, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 8, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 8, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 8, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 8, 2022)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (July 8, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 8, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 8, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 8, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Waiver has been granted (June 8, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 8, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 8, 2022)

February 26, 2020 — 16 citations

Citations issued on February 26, 2020
TagWhat the surveyor checksStatus
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (February 14, 2020)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (February 14, 2020)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (February 14, 2020)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 14, 2020)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (February 14, 2020)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 14, 2020)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 14, 2020)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (February 14, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 14, 2020)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 14, 2020)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 14, 2020)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 14, 2020)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (February 14, 2020)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (February 14, 2020)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Waiver has been granted (February 14, 2020)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 14, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.