Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CITIZENS MEDICAL CENTER LTCU

COLBY, KS · 60 certified beds · Last Life Safety survey July 8, 2026

CMS Certification Number 175554 · first certified January 2017

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

26
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
7
Tags cited more than once
Across separate surveys
12
Inspection & testing records
Of the citations on file

Position within KS

26 citations — more than 45% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 10 citations; the earlier surveys on file averaged 8. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2028 — about 16 months from now. This facility’s last Life Safety survey was July 2026. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 290 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about CITIZENS MEDICAL CENTER LTCU

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 26 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

How that compares

Citations in CMS's current file

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility26KS median27National median11
Citations in CMS's current file, compared
MeasureCitations
This facility26
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
72022-1092024-08102026-07
Citations at each Life Safety survey
Survey dateCitations
October 13, 20227
August 7, 20249
July 8, 202610

Most-cited tags

Most-cited tags at this facility
K-05112K-09202K-09182E-00392K-03212K-03452K-03532K-03631
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0511Have properly installed electrical wiring and gas equipment.22024-08-07
K-0920Ensure proper usage of power strips and extension cords.22024-08-07
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-07-08
E-0039Conduct testing and exercise requirements.22026-07-08
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22026-07-08
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22024-08-07
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-07-08
K-0363Install corridor and hallway doors that block smoke.12022-10-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Emergency Preparedness Deficiencies 4
  • Services Deficiencies 3
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Gas, Vacuum, and Electrical Systems Deficiencies5
Emergency Preparedness Deficiencies4
Services Deficiencies3
Egress Deficiencies2
Miscellaneous Deficiencies1
Electrical Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 8, 2026 — 10 citations

Citations issued on July 8, 2026
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has no plan of correction
E-0039Conduct testing and exercise requirements.Deficient, Provider has no plan of correction
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has no plan of correction
K-0300Meet other general requirements that are deficient.Deficient, Provider has no plan of correction
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has no plan of correction
K-0331Construct fire resistant interior walls.Deficient, Provider has no plan of correction
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.Deficient, Provider has no plan of correction
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has no plan of correction
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has no plan of correction
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has no plan of correction

August 7, 2024 — 9 citations

Citations issued on August 7, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (September 18, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 18, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 18, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 18, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 18, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 18, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 18, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 18, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 18, 2024)

October 13, 2022 — 7 citations

Citations issued on October 13, 2022
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 8, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 8, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 8, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 8, 2022)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (December 8, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 8, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (December 8, 2022)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.