Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

LAWRENCE PRESBYTERIAN MANOR

LAWRENCE, KS · 40 certified beds · Last Life Safety survey February 18, 2026

CMS Certification Number 175305 · first certified July 1994

Ownership

Operated by PRESBYTERIAN MANORS OF MID-AMERICA · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

17
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
3
Tags cited more than once
Across separate surveys
10
Inspection & testing records
Of the citations on file

Position within KS

17 citations — more than 15% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 7 citations; the earlier surveys in the window averaged 5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens October 2027 — about 12 months from now. This facility’s last Life Safety survey was February 2026. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about LAWRENCE PRESBYTERIAN MANOR

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 17 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 17 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility17KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility17
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
52022-1152024-0572026-02
Citations at each Life Safety survey
Survey dateCitations
November 2, 20225
May 8, 20245
February 18, 20267

Most-cited tags

Most-cited tags at this facility
K-03532K-03542K-03452K-07611E-00041K-02931K-03471K-03241
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-02-18
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.22026-02-18
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22026-02-18
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.12026-02-18
E-0004Develop and maintain an Emergency Preparedness Program (EP).12026-02-18
K-0293Have properly located and lighted "Exit" signs.12022-11-02
K-0347Properly provide smoke detection systems in areas open to corridors.12024-05-08
K-0324Provide properly protected cooking facilities.12024-05-08

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Egress Deficiencies 3
  • Services Deficiencies 1
  • Miscellaneous Deficiencies 1
  • Other 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Egress Deficiencies3
Services Deficiencies1
Miscellaneous Deficiencies1
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 18, 2026 — 7 citations

Citations issued on February 18, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (March 17, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 19, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 19, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 19, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 19, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (March 26, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (March 31, 2026)

May 8, 2024 — 5 citations

Citations issued on May 8, 2024
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 1, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 1, 2024)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (July 1, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (July 17, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 1, 2024)

November 2, 2022 — 5 citations

Citations issued on November 2, 2022
TagWhat the surveyor checksStatus
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (January 20, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 20, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 20, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 20, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 20, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.