Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

NEODESHA CARE AND REHAB

NEODESHA, KS · 45 certified beds · Last Life Safety survey April 14, 2026

CMS Certification Number 175317 · first certified August 1994

Ownership

Operated by MISSION HEALTH COMMUNITIES · For profit - Limited Liability company

  • Ownership changed October 1, 2019 (change of ownership)from NEODESHA CARE AND REHABILITATION CENTER LLC
31
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
21
Inspection & testing records
Of the citations on file

Position within KS

31 citations — more than 64% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 11. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2027 — about 14 months from now. This facility’s last Life Safety survey was April 2026. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about NEODESHA CARE AND REHAB

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 31 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility31KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility31
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
122022-11102024-0692026-04
Citations at each Life Safety survey
Survey dateCitations
November 30, 202212
June 12, 202410
April 14, 20269

Most-cited tags

Most-cited tags at this facility
K-07123K-09183K-03533K-05113K-02222K-07412K-09232K-03722
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32026-04-14
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-04-14
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-04-14
K-0511Have properly installed electrical wiring and gas equipment.32026-04-14
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22026-04-14
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22024-06-12
K-0923Have proper medical gas storage and administration areas.22026-04-14
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-04-14

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Miscellaneous Deficiencies 6
  • Egress Deficiencies 4
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Gas, Vacuum, and Electrical Systems Deficiencies7
Miscellaneous Deficiencies6
Egress Deficiencies4
Services Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 14, 2026 — 9 citations

Citations issued on April 14, 2026
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 16, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 16, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 18, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 16, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 16, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 18, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 18, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 16, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 16, 2026)

June 12, 2024 — 10 citations

Citations issued on June 12, 2024
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 31, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 31, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (July 15, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 31, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 31, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 31, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 31, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 31, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 31, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 31, 2024)

November 30, 2022 — 12 citations

Citations issued on November 30, 2022
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (January 25, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 25, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (January 25, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 25, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 25, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 25, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (January 25, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 25, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 25, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 25, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 25, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 25, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.