Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

COUNTRYSIDE HEALTH CENTER

TOPEKA, KS · 97 certified beds · Last Life Safety survey April 30, 2025

CMS Certification Number 17E528 · first certified December 1982

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

33
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
13
Inspection & testing records
Of the citations on file

Position within KS

33 citations — more than 70% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2026 — about 3 months from now. This facility’s last Life Safety survey was April 2025. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about COUNTRYSIDE HEALTH CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

8 of the 33 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 33 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility33KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility33
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
102022-01172023-0862025-04
Citations at each Life Safety survey
Survey dateCitations
January 10, 202210
August 15, 202317
April 30, 20256

Most-cited tags

Most-cited tags at this facility
K-03533K-03452K-03542K-02112K-07412K-07122K-02222K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-04-30
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-04-30
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.22025-04-30
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22023-08-15
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22023-08-15
K-0712Have simulated fire drills held at unexpected times.22023-08-15
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22023-08-15
K-0324Provide properly protected cooking facilities.22023-08-15

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Emergency Preparedness Deficiencies 8
  • Miscellaneous Deficiencies 6
  • Egress Deficiencies 4
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Emergency Preparedness Deficiencies8
Miscellaneous Deficiencies6
Egress Deficiencies4
Gas, Vacuum, and Electrical Systems Deficiencies2
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 30, 2025 — 6 citations

Citations issued on April 30, 2025
TagWhat the surveyor checksStatus
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (July 9, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 2, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 7, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (July 2, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 2, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 7, 2025)

August 15, 2023 — 17 citations

Citations issued on August 15, 2023
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (October 27, 2023)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (October 27, 2023)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 27, 2023)
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (October 27, 2023)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (October 27, 2023)
E-0029Develop a communication plan.Deficient, Provider has date of correction (October 27, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 27, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 27, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 27, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 27, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 27, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 27, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 27, 2023)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (October 27, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 27, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 27, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 27, 2023)

January 10, 2022 — 10 citations

Citations issued on January 10, 2022
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 16, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 16, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 16, 2022)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (March 16, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 16, 2022)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (March 16, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 16, 2022)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 16, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 16, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 16, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.