Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

TREGO CO-LEMKE MEMORIAL HOSPITAL LTCU

WAKEENEY, KS · 37 certified beds · Last Life Safety survey June 4, 2025

CMS Certification Number 17A020 · first certified March 1974

Ownership

Independently operated (no chain recorded by CMS) · Government - County

No change of ownership on CMS record since January 1, 2016, when the records begin.

41
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
26
Inspection & testing records
Of the citations on file

Position within KS

41 citations — more than 86% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 13 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was June 2025. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about TREGO CO-LEMKE MEMORIAL HOSPITAL LTCU

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility41KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility41
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
152022-05132023-09132025-06
Citations at each Life Safety survey
Survey dateCitations
May 26, 202215
September 20, 202313
June 4, 202513

Most-cited tags

Most-cited tags at this facility
K-03553K-09203K-09183K-03453K-07123K-07613K-05113K-03532
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.32025-06-04
K-0920Ensure proper usage of power strips and extension cords.32025-06-04
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-06-04
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-06-04
K-0712Have simulated fire drills held at unexpected times.32025-06-04
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32025-06-04
K-0511Have properly installed electrical wiring and gas equipment.32025-06-04
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-06-04

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Miscellaneous Deficiencies 8
  • Egress Deficiencies 5
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies10
Miscellaneous Deficiencies8
Egress Deficiencies5
Services Deficiencies3
Electrical Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 4, 2025 — 13 citations

Citations issued on June 4, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 30, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 30, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 30, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 30, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 30, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 30, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 30, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 30, 2025)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (July 30, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 30, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 30, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 30, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 30, 2025)

September 20, 2023 — 13 citations

Citations issued on September 20, 2023
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 2, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (November 2, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 2, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 2, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (November 2, 2023)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (November 2, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 2, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 2, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 2, 2023)
K-0908Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.Deficient, Provider has date of correction (November 2, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 2, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 2, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 2, 2023)

May 26, 2022 — 15 citations

Citations issued on May 26, 2022
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (July 16, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 27, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 25, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 23, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 19, 2022)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (July 21, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 21, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 11, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 27, 2022)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (July 16, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 16, 2022)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (July 28, 2022)
K-0908Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.Deficient, Provider has date of correction (July 22, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 23, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 18, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.