Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
Laurel Heights Home for the Elderly
London, KY · 160 certified beds · Last Life Safety survey April 3, 2025
CMS Certification Number 185003 · first certified January 1967
Ownership
Independently operated (no chain recorded by CMS) · Non profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within KY
9 citations — more than 54% of the 267 certified nursing homes in KY. Compared within KY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
When is the next survey likely?
The window is open now: May 2026 to March 2030. This facility’s last Life Safety survey was April 2025. Facilities in KY are typically surveyed 14–59 months after the last one (median 28), measured over 391 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about Laurel Heights Home for the Elderly
One email when it happens. No account; stop it any time with one click.
How that compares
Compared with the median facility in KY, and nationally. Surveyors differ markedly between states, so the KY figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 9 |
| Median facility in KY | 7 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| January 10, 2019 | 0 |
| March 5, 2020 | 0 |
| April 3, 2025 | 9 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0351 | Install an approved automatic sprinkler system. | 1 | 2025-04-03 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 1 | 2025-04-03 |
| K-0363 | Install corridor and hallway doors that block smoke. | 1 | 2025-04-03 |
| K-0324 | Provide properly protected cooking facilities. | 1 | 2025-04-03 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 1 | 2025-04-03 |
| K-0781 | Have restrictions on the use of portable space heaters. | 1 | 2025-04-03 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 1 | 2025-04-03 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 1 | 2025-04-03 |
What the citations cover
- Smoke Deficiencies 5
- Gas, Vacuum, and Electrical Systems Deficiencies 3
- Miscellaneous Deficiencies 1
| Category | Citations |
|---|---|
| Smoke Deficiencies | 5 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 3 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 3, 2025 — 9 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (May 12, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (May 14, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 21, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (May 30, 2025) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (May 30, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (April 24, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (May 30, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (May 12, 2025) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.