Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Mission Point Nursing & Physical Rehabilitation Ce

Detroit, MI · 120 certified beds · Last Life Safety survey January 29, 2026

CMS Certification Number 235454 · first certified June 1986

Ownership

Operated by MISSION POINT HEALTHCARE SERVICES · For profit - Individual

  • Ownership changed December 17, 2020 (change of ownership)to MISSION POINT NURSING & PHYSICAL REHABILITATION CENTER OF ELMWOOD from THE BAY AT ELMWOOD HEALTH AND REHABILITATION CENTER, LLC
36
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within MI

36 citations — more than 96% of the 422 certified nursing homes in MI. Compared within MI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 5 citations; the earlier surveys in the window averaged 10.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was January 2026. Facilities in MI are typically surveyed 12–14 months after the last one (median 13), measured over 723 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Mission Point Nursing & Physical Rehabilitation Ce

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 36 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 36 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0908 Keep all essential equipment working safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in MI, and nationally. Surveyors differ markedly between states, so the MI figure is the meaningful one.

This facility36MI median14National median11
Citations on file over three years, compared
MeasureCitations
This facility36
Median facility in MI14
Median facility nationally11

Survey history

Citations at each Life Safety survey
72023-08182024-0862025-0852026-01
Citations at each Life Safety survey
Survey dateCitations
August 2, 20237
August 8, 202418
August 25, 20256
January 29, 20265

Most-cited tags

Most-cited tags at this facility
K-03534K-03453K-03213K-07122K-02112K-03242K-09182K-05212
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.42026-01-29
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-08-25
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32026-01-29
K-0712Have simulated fire drills held at unexpected times.22024-08-08
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22025-08-25
K-0324Provide properly protected cooking facilities.22024-08-08
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-01-29
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22025-08-25

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 18
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Miscellaneous Deficiencies 4
  • Egress Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies18
Gas, Vacuum, and Electrical Systems Deficiencies5
Miscellaneous Deficiencies4
Egress Deficiencies4
Services Deficiencies3
Emergency Preparedness Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 29, 2026 — 5 citations

Citations issued on January 29, 2026
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 8, 2026)
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.Deficient, Provider has date of correction (April 8, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 8, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (April 8, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 8, 2026)

August 25, 2025 — 6 citations

Citations issued on August 25, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 3, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 24, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 3, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 3, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (October 3, 2025)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (October 3, 2025)

August 8, 2024 — 18 citations

Citations issued on August 8, 2024
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (September 30, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 30, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (September 30, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 7, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 30, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 30, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 30, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 30, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (September 30, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 30, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 30, 2024)
K-0371Have properly sized and located compartments to protect residents from smoke.Deficient, Provider has date of correction (October 7, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (September 30, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (September 30, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 30, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (September 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 30, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (September 30, 2024)

August 2, 2023 — 7 citations

Citations issued on August 2, 2023
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 15, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 15, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 15, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 15, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 15, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 15, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 15, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.