Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Milford Meadows Care Center

Milford, NE · 80 certified beds · Last Life Safety survey February 11, 2025

CMS Certification Number 285232 · first certified September 1998

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

40
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
12
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within NE

40 citations — more than 94% of the 180 certified nursing homes in NE. Compared within NE rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Holding steadyabout the same at the latest survey as at its earlier surveys in the window.

The latest survey found 13 citations; the earlier surveys in the window averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (February 2026 to April 2026), and past the point by which nine in ten NE facilities have been surveyed. This facility’s last Life Safety survey was February 2025. Facilities in NE are typically surveyed 12–14 months after the last one (median 13), measured over 271 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Milford Meadows Care Center

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 40 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NE, and nationally. Surveyors differ markedly between states, so the NE figure is the meaningful one.

This facility40NE median15National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in NE15
Median facility nationally11

Survey history

Citations at each Life Safety survey
162023-05112024-04132025-02
Citations at each Life Safety survey
Survey dateCitations
May 16, 202316
April 2, 202411
February 11, 202513

Most-cited tags

Most-cited tags at this facility
K-09213K-03633K-09182E-00412K-03212K-09192K-07412K-09222
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0921Ensure that testing and maintenance of electrical equipment is performed.32025-02-11
K-0363Install corridor and hallway doors that block smoke.32025-02-11
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-04-02
E-0041Implement emergency and standby power systems.22024-04-02
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22025-02-11
K-0919Meet requirements for the use of electrical equipment.22024-04-02
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22025-02-11
K-0922Meet requirements for the use and maintenance of medical gas equipment.22025-02-11

What the citations cover

Citations by CMS category
  • Gas, Vacuum, and Electrical Systems Deficiencies 13
  • Smoke Deficiencies 9
  • Miscellaneous Deficiencies 8
  • Services Deficiencies 3
  • Other 7
Citations by CMS category
CategoryCitations
Gas, Vacuum, and Electrical Systems Deficiencies13
Smoke Deficiencies9
Miscellaneous Deficiencies8
Services Deficiencies3
Egress Deficiencies3
Emergency Preparedness Deficiencies2
Construction Deficiencies1
Electrical Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 11, 2025 — 13 citations

Citations issued on February 11, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 28, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 28, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 28, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 28, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 28, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 28, 2025)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (March 28, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 28, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 28, 2025)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (March 28, 2025)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (March 28, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (March 28, 2025)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (March 28, 2025)

April 2, 2024 — 11 citations

Citations issued on April 2, 2024
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (May 17, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 17, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (May 17, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 17, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 17, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 17, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 17, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (May 17, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 17, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (May 17, 2024)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (May 17, 2024)

May 16, 2023 — 16 citations

Citations issued on May 16, 2023
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (June 30, 2023)
K-0132Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.Deficient, Provider has date of correction (June 30, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 30, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 30, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 30, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 30, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 30, 2023)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (June 30, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (June 30, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 30, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (June 30, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 30, 2023)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (June 30, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 30, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (June 30, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 30, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.