Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

NEW JERSEY VETERANS MEMORIAL HOME MENLO

EDISON, NJ · 328 certified beds · Last Life Safety survey September 5, 2025

CMS Certification Number 315459 · first certified October 1999

Ownership

Independently operated (no chain recorded by CMS) · Government - State

No change of ownership on CMS record since January 1, 2016, when the records begin.

23
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
12
Inspection & testing records
Of the citations on file

Position within NJ

23 citations — more than 84% of the 348 certified nursing homes in NJ. Compared within NJ rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 4 citations; the earlier surveys in the window averaged 9.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2026 — about 3 months from now. This facility’s last Life Safety survey was September 2025. Facilities in NJ are typically surveyed 16–20 months after the last one (median 17), measured over 431 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about NEW JERSEY VETERANS MEMORIAL HOME MENLO

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 23 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NJ, and nationally. Surveyors differ markedly between states, so the NJ figure is the meaningful one.

This facility23NJ median15National median11
Citations on file over three years, compared
MeasureCitations
This facility23
Median facility in NJ15
Median facility nationally11

Survey history

Citations at each Life Safety survey
112022-0982024-0742025-09
Citations at each Life Safety survey
Survey dateCitations
September 8, 202211
July 16, 20248
September 5, 20254

Most-cited tags

Most-cited tags at this facility
K-03632K-03412K-02932K-09182K-03532K-02231K-03551K-02911
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.22024-07-16
K-0341Install a fire alarm system that can be heard throughout the facility.22025-09-05
K-0293Have properly located and lighted "Exit" signs.22024-07-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-07-16
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-09-05
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.12024-07-16
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12022-09-08
K-0291Install emergency lighting that can last at least 1 1/2 hours.12022-09-08

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Egress Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
  • Services Deficiencies 2
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Egress Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies3
Services Deficiencies2
Miscellaneous Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

September 5, 2025 — 4 citations

Citations issued on September 5, 2025
TagWhat the surveyor checksStatus
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (October 24, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 24, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 25, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 30, 2025)

July 16, 2024 — 8 citations

Citations issued on July 16, 2024
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (August 19, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 19, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 19, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 19, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 19, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (August 19, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 19, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 19, 2024)

September 8, 2022 — 11 citations

Citations issued on September 8, 2022
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 6, 2022)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (October 6, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 19, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 7, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 7, 2022)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (December 18, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 6, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 7, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 6, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (October 28, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 18, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.