Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
VALLEY VIEW REHABILITATION AND HEALTHCARE CTR
NEWTON, NJ · 31 certified beds · Last Life Safety survey April 24, 2025
CMS Certification Number 315409 · first certified January 1998
Ownership
Independently operated (no chain recorded by CMS) · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within NJ
27 citations — more than 89% of the 348 certified nursing homes in NJ. Compared within NJ rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 14 citations; the earlier surveys in the window averaged 6.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: August 2026 to January 2027. This facility’s last Life Safety survey was April 2025. Facilities in NJ are typically surveyed 16–20 months after the last one (median 17), measured over 431 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about VALLEY VIEW REHABILITATION AND HEALTHCARE CTR
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
4 of the 27 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 27 Life Safety citations above. The Physical Environment Index
- F-0880 Provide and implement an infection prevention and control program.
How that compares
Compared with the median facility in NJ, and nationally. Surveyors differ markedly between states, so the NJ figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 27 |
| Median facility in NJ | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| July 29, 2021 | 3 |
| November 22, 2023 | 10 |
| April 24, 2025 | 14 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0252 | Provide at least two remote exits on each floor or fire section of the building. | 3 | 2025-04-24 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2025-04-24 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-04-24 |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | 2 | 2025-04-24 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2025-04-24 |
| K-0351 | Install an approved automatic sprinkler system. | 2 | 2025-04-24 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2 | 2025-04-24 |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | 2 | 2025-04-24 |
What the citations cover
- Smoke Deficiencies 10
- Egress Deficiencies 7
- Gas, Vacuum, and Electrical Systems Deficiencies 5
- Emergency Preparedness Deficiencies 4
- Other 1
| Category | Citations |
|---|---|
| Smoke Deficiencies | 10 |
| Egress Deficiencies | 7 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 5 |
| Emergency Preparedness Deficiencies | 4 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 24, 2025 — 14 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (May 16, 2025) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (May 17, 2025) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (May 17, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (May 16, 2025) |
| K-0252 | Provide at least two remote exits on each floor or fire section of the building. | Deficient, Provider has date of correction (May 17, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (May 16, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 14, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (May 16, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 14, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (May 16, 2025) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (May 15, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (May 16, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (May 16, 2025) |
November 22, 2023 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (December 15, 2023) |
| K-0252 | Provide at least two remote exits on each floor or fire section of the building. | Waiver has been granted (December 29, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (December 29, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (December 29, 2023) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (January 30, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (December 29, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (December 29, 2023) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (December 8, 2023) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (December 8, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (January 30, 2024) |
July 29, 2021 — 3 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0252 | Provide at least two remote exits on each floor or fire section of the building. | Waiver has been granted (November 20, 2021) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (August 6, 2021) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 6, 2021) |