Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

COLLEGE PARK REHABILITATION CENTER

NORTH LAS VEGAS, NV · 188 certified beds · Last Life Safety survey November 24, 2025

CMS Certification Number 295055 · first certified September 1994

Ownership

Operated by FUNDAMENTAL HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

55
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
15
Tags cited more than once
Across separate surveys
23
Inspection & testing records
Of the citations on file

Position within NV

55 citations — more than 99% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 21 citations; the earlier surveys in the window averaged 17. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 1 month from now. This facility’s last Life Safety survey was November 2025. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 117 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about COLLEGE PARK REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

12 of the 55 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 55 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.

This facility55NV median26National median11
Citations on file over three years, compared
MeasureCitations
This facility55
Median facility in NV26
Median facility nationally11

Survey history

Citations at each Life Safety survey
192023-07152024-09212025-11
Citations at each Life Safety survey
Survey dateCitations
July 13, 202319
September 27, 202415
November 24, 202521

Most-cited tags

Most-cited tags at this facility
K-09183K-03533K-03453K-03552K-03242K-02112K-05112K-07412
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-11-24
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-11-24
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-11-24
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-11-24
K-0324Provide properly protected cooking facilities.22025-11-24
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22024-09-27
K-0511Have properly installed electrical wiring and gas equipment.22025-11-24
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22024-09-27

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 17
  • Emergency Preparedness Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 11
  • Egress Deficiencies 6
  • Other 9
Citations by CMS category
CategoryCitations
Smoke Deficiencies17
Emergency Preparedness Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies11
Egress Deficiencies6
Miscellaneous Deficiencies5
Services Deficiencies3
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 24, 2025 — 21 citations

Citations issued on November 24, 2025
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (January 26, 2026)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (January 4, 2026)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (January 4, 2026)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (January 4, 2026)
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (January 4, 2026)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (January 4, 2026)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (January 4, 2026)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (January 4, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (January 4, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 11, 2026)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (December 19, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 4, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 2, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 4, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 22, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (January 4, 2026)
K-0908Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.Deficient, Provider has date of correction (February 16, 2026)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (December 19, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (December 22, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 20, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (December 19, 2025)

September 27, 2024 — 15 citations

Citations issued on September 27, 2024
TagWhat the surveyor checksStatus
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (November 6, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 6, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (November 6, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 6, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 6, 2024)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (November 6, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 6, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 6, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (November 6, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 6, 2024)
K-0371Have properly sized and located compartments to protect residents from smoke.Deficient, Provider has date of correction (November 6, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 6, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 6, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 6, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 6, 2024)

July 13, 2023 — 19 citations

Citations issued on July 13, 2023
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (September 14, 2023)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (September 14, 2023)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (September 14, 2023)
K-0100Meet other general requirements.Deficient, Provider has date of correction (September 14, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (September 14, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (September 14, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 14, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 10, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 14, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 10, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 14, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (October 10, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 14, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 10, 2023)
K-0902Meet requirements for the installation and maintenance of medical gas and medical vacuum systems.Deficient, Provider has date of correction (September 14, 2023)
K-0904Have a properly installed medical gas master alarm panel.Deficient, Provider has date of correction (October 10, 2023)
K-0906Ensure gas cylinders are properly stored.Deficient, Provider has date of correction (October 10, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 10, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (September 14, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.