Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

University Center for Rehabilitation and Nursing

Bronx, NY · 46 certified beds · Last Life Safety survey March 25, 2026

CMS Certification Number 335061 · first certified April 1969

Ownership

Operated by CENTERS HEALTH CARE · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

27
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
3
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within NY

27 citations — more than 87% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 6.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens September 2027 — about 12 months from now. This facility’s last Life Safety survey was March 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about University Center for Rehabilitation and Nursing

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 27 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

How that compares

Citations on file over three years

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility27NY median13National median11
Citations on file over three years, compared
MeasureCitations
This facility27
Median facility in NY13
Median facility nationally11

Survey history

Citations at each Life Safety survey
82022-1152024-05142026-03
Citations at each Life Safety survey
Survey dateCitations
November 22, 20228
May 7, 20245
March 25, 202614

Most-cited tags

Most-cited tags at this facility
K-09183K-02812K-02912K-09151K-03241K-03551K-02711K-02251
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-03-25
K-0281Install proper backup exit lighting.22026-03-25
K-0291Install emergency lighting that can last at least 1 1/2 hours.22026-03-25
K-0915Have proper power supply for life support equipment.12022-11-22
K-0324Provide properly protected cooking facilities.12026-03-25
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12026-03-25
K-0271Have exits that are accessible at all times.12026-03-25
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.12026-03-25

What the citations cover

Citations by CMS category
  • Egress Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Smoke Deficiencies 6
  • Emergency Preparedness Deficiencies 3
  • Other 3
Citations by CMS category
CategoryCitations
Egress Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies7
Smoke Deficiencies6
Emergency Preparedness Deficiencies3
Miscellaneous Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 25, 2026 — 14 citations

Citations issued on March 25, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (May 7, 2026)
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (May 7, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 7, 2026)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (May 7, 2026)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (May 7, 2026)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (May 7, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 7, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 7, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 7, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 7, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 7, 2026)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (May 7, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 7, 2026)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (May 7, 2026)

May 7, 2024 — 5 citations

Citations issued on May 7, 2024
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 23, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 23, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 23, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 23, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 23, 2024)

November 22, 2022 — 8 citations

Citations issued on November 22, 2022
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (December 29, 2022)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 20, 2022)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (December 29, 2022)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (January 12, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (December 28, 2022)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (December 31, 2022)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (January 12, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 29, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.