Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BEACHWOOD POINTE CARE CENTER

BEACHWOOD, OH · 120 certified beds · Last Life Safety survey July 23, 2024

CMS Certification Number 365071 · first certified January 1967

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

  • Ownership changed August 2, 2021 (change of ownership)from BROOK POINTE HEALTH AND REHAB, INC.
40
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within OH

40 citations — more than 96% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 17 citations; the earlier surveys in the window averaged 11.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: March 2026 to March 2027. This facility’s last Life Safety survey was July 2024. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BEACHWOOD POINTE CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 40 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility40OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-05142022-04172024-07
Citations at each Life Safety survey
Survey dateCitations
May 9, 20199
April 11, 202214
July 23, 202417

Most-cited tags

Most-cited tags at this facility
K-07123K-03632K-03532K-02222K-09182K-03452K-03512K-03552
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32024-07-23
K-0363Install corridor and hallway doors that block smoke.22024-07-23
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-07-23
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22024-07-23
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-07-23
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22022-04-11
K-0351Install an approved automatic sprinkler system.22024-07-23
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22024-07-23

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Egress Deficiencies 8
  • Miscellaneous Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Egress Deficiencies8
Miscellaneous Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies6
Emergency Preparedness Deficiencies2
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 23, 2024 — 17 citations

Citations issued on July 23, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 24, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (September 24, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 10, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 24, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (November 13, 2024)
K-0351Install an approved automatic sprinkler system.Waiver has been granted (January 15, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 24, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 24, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (November 13, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 24, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (September 24, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 24, 2024)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (September 24, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 24, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 24, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 13, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 13, 2024)

April 11, 2022 — 14 citations

Citations issued on April 11, 2022
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 15, 2022)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (April 15, 2022)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (April 15, 2022)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (April 15, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 15, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 15, 2022)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (April 15, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 15, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (April 15, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 15, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (April 15, 2022)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (April 15, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 15, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 15, 2022)

May 9, 2019 — 9 citations

Citations issued on May 9, 2019
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has plan of correction (June 24, 2019)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has plan of correction (June 24, 2019)
K-0226Have horizontal exits used in accordance with safety requirements.Deficient, Provider has date of correction (June 24, 2019)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 24, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 24, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 24, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 24, 2019)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 24, 2019)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 24, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.