9
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
1
Tags cited more than once
Across separate surveys
7
Inspection & testing records
Of the citations on file

Position within OH

9 citations — more than 19% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 2 citations; the earlier surveys in the window averaged 3.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (September 2024 to September 2025), and past the point by which nine in ten OH facilities have been surveyed. This facility’s last Life Safety survey was January 2023. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about LOGAN ACRES

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 9 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility9OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility9
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
62018-0812019-1022023-01
Citations at each Life Safety survey
Survey dateCitations
August 29, 20186
October 17, 20191
January 26, 20232

Most-cited tags

Most-cited tags at this facility
K-09182K-03551K-03471K-03531K-07611K-09141K-05111K-03451
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.22023-01-26
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12018-08-29
K-0347Properly provide smoke detection systems in areas open to corridors.12023-01-26
K-0353Inspect, test, and maintain automatic sprinkler systems.12018-08-29
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.12018-08-29
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.12018-08-29
K-0511Have properly installed electrical wiring and gas equipment.12018-08-29
K-0345Have approved installation, maintenance and testing program for fire alarm systems.12018-08-29

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 4
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
  • Miscellaneous Deficiencies 1
  • Services Deficiencies 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies4
Gas, Vacuum, and Electrical Systems Deficiencies3
Miscellaneous Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 26, 2023 — 2 citations

Citations issued on January 26, 2023
TagWhat the surveyor checksStatus
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (February 28, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 28, 2023)

October 17, 2019 — 1 citation

Citations issued on October 17, 2019
TagWhat the surveyor checksStatus
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 11, 2019)

August 29, 2018 — 6 citations

Citations issued on August 29, 2018
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 28, 2018)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 5, 2018)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 5, 2018)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 5, 2018)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 5, 2018)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 5, 2018)