Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
EAST PARK CARE CENTER
BROOK PARK, OH · 57 certified beds · Last Life Safety survey October 28, 2024
CMS Certification Number 365731 · first certified March 1989
Ownership
Operated by LIONSTONE CARE · For profit - Corporation
- Ownership changed October 29, 2021 (change of ownership)from EAST PARK RETIREMENT COMMUNITY INC
Position within OH
43 citations — more than 98% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 17 citations; the earlier surveys in the window averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: June 2026 to June 2027. This facility’s last Life Safety survey was October 2024. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about EAST PARK CARE CENTER
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
9 of the 43 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 43 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 43 |
| Median facility in OH | 16 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| May 30, 2019 | 17 |
| May 5, 2022 | 9 |
| October 28, 2024 | 17 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2024-10-28 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2024-10-28 |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | 2 | 2024-10-28 |
| K-0351 | Install an approved automatic sprinkler system. | 2 | 2024-10-28 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2024-10-28 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 2 | 2024-10-28 |
| E-0034 | Provide a means of sharing information on occupancy/needs. | 1 | 2019-05-30 |
| E-0036 | Establish emergency prep training and testing. | 1 | 2019-05-30 |
What the citations cover
- Smoke Deficiencies 12
- Emergency Preparedness Deficiencies 9
- Gas, Vacuum, and Electrical Systems Deficiencies 7
- Miscellaneous Deficiencies 5
- Other 10
| Category | Citations |
|---|---|
| Smoke Deficiencies | 12 |
| Emergency Preparedness Deficiencies | 9 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 7 |
| Miscellaneous Deficiencies | 5 |
| Services Deficiencies | 4 |
| Egress Deficiencies | 4 |
| Construction Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
October 28, 2024 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0344 | Have an alternate power supply for its alarm system. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (November 21, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (November 21, 2024) |
May 5, 2022 — 9 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0132 | Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (May 30, 2022) |
| K-0930 | Ensure proper storage of liquid oxygen. | Deficient, Provider has date of correction (May 30, 2022) |
May 30, 2019 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (August 6, 2019) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (August 6, 2019) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (August 6, 2019) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (August 6, 2019) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (August 6, 2019) |
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has date of correction (August 6, 2019) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (August 6, 2019) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0227 | Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (August 6, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 6, 2019) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.