Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PARKSIDE NURSING AND REHABILITATION CENTER

FAIRFIELD, OH · 76 certified beds · Last Life Safety survey July 31, 2025

CMS Certification Number 365363 · first certified January 1978

Ownership

Operated by EMBASSY HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

41
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
25
Inspection & testing records
Of the citations on file

Position within OH

41 citations — more than 97% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 17 citations; the earlier surveys in the window averaged 12. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 6 months from now. This facility’s last Life Safety survey was July 2025. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PARKSIDE NURSING AND REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

11 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 41 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility41OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility41
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
82019-11162022-06172025-07
Citations at each Life Safety survey
Survey dateCitations
November 14, 20198
June 27, 202216
July 31, 202517

Most-cited tags

Most-cited tags at this facility
K-03723K-07413K-03533K-07112K-05212K-05112K-03242K-07122
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32025-07-31
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32025-07-31
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-07-31
K-0711Provide a written emergency evacuation plan.22025-07-31
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22025-07-31
K-0511Have properly installed electrical wiring and gas equipment.22025-07-31
K-0324Provide properly protected cooking facilities.22025-07-31
K-0712Have simulated fire drills held at unexpected times.22025-07-31

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Miscellaneous Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Services Deficiencies 4
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Miscellaneous Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies7
Services Deficiencies4
Egress Deficiencies4
Construction Deficiencies2
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 31, 2025 — 17 citations

Citations issued on July 31, 2025
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (August 25, 2025)
K-0132Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.Deficient, Provider has date of correction (August 25, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 25, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 25, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 25, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 25, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 25, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 25, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 25, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 25, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 25, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (August 25, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 25, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 25, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 25, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (August 25, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 25, 2025)

June 27, 2022 — 16 citations

Citations issued on June 27, 2022
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (July 30, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 30, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 30, 2022)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (July 30, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 30, 2022)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (July 30, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 30, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 30, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 30, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 30, 2022)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (July 30, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 30, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 30, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 30, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 30, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 30, 2022)

November 14, 2019 — 8 citations

Citations issued on November 14, 2019
TagWhat the surveyor checksStatus
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Waiver has been granted (January 6, 2020)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 3, 2020)
K-0363Install corridor and hallway doors that block smoke.Waiver has been granted (January 6, 2020)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 3, 2020)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 3, 2020)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 3, 2020)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 3, 2020)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 3, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.