Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CEDARVIEW CARE CENTER

LEBANON, OH · 83 certified beds · Last Life Safety survey March 19, 2026

CMS Certification Number 365690 · first certified December 1986

Ownership

Operated by CCH HEALTHCARE · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

32
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
9
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within OH

32 citations — more than 89% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 7 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2027 — about 13 months from now. This facility’s last Life Safety survey was March 2026. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about CEDARVIEW CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 32 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility32OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility32
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
162023-0692024-0472026-03
Citations at each Life Safety survey
Survey dateCitations
June 28, 202316
April 18, 20249
March 19, 20267

Most-cited tags

Most-cited tags at this facility
K-03453K-09153K-03533K-07412K-02912K-09182K-09202K-02232
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32026-03-19
K-0915Have proper power supply for life support equipment.32026-03-19
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-03-19
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22026-03-19
K-0291Install emergency lighting that can last at least 1 1/2 hours.22026-03-19
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-04-18
K-0920Ensure proper usage of power strips and extension cords.22024-04-18
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.22024-04-18

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 7
  • Miscellaneous Deficiencies 2
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies7
Miscellaneous Deficiencies2
Construction Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 19, 2026 — 7 citations

Citations issued on March 19, 2026
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 13, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 13, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 13, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 13, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (April 13, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (April 13, 2026)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (April 13, 2026)

April 18, 2024 — 9 citations

Citations issued on April 18, 2024
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (May 16, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 16, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (May 16, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 16, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 16, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 16, 2024)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (May 16, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 16, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 16, 2024)

June 28, 2023 — 16 citations

Citations issued on June 28, 2023
TagWhat the surveyor checksStatus
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has date of correction (August 9, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 9, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 9, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 9, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 9, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 9, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (August 9, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 9, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (August 9, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 9, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 9, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 9, 2023)
K-0915Have proper power supply for life support equipment.Waiver has been granted (May 16, 2024)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (August 9, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 9, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 9, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.