Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

ROLLING FIELDS, INC

CONNEAUTVILLE, PA · 181 certified beds · Last Life Safety survey November 18, 2025

CMS Certification Number 395619 · first certified January 1984

Ownership

Operated by HERITAGE MINISTRIES · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

37
Citations on file
Rolling three-year window
6
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within PA

37 citations — more than 98% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 5. With 6 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens September 2026. This facility’s last Life Safety survey was November 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about ROLLING FIELDS, INC

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 37 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 37 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility37PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility37
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
82023-1142024-0912024-09112024-1012025-01122025-11
Citations at each Life Safety survey
Survey dateCitations
November 2, 20238
September 19, 20244
September 20, 20241
October 31, 202411
January 8, 20251
November 18, 202512

Most-cited tags

Most-cited tags at this facility
K-09113K-09183K-03453K-03243K-03553K-03533K-09122K-03722
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0911Meet requirements for the installation and maintenance of electrical systems.32025-11-18
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-11-18
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-11-18
K-0324Provide properly protected cooking facilities.32025-11-18
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.32025-11-18
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-11-18
K-0912Have power receptacles that are properly grounded.22025-11-18
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22025-11-18

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 18
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 5
  • Construction Deficiencies 2
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies18
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies5
Construction Deficiencies2
Miscellaneous Deficiencies2
Services Deficiencies1
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 18, 2025 — 12 citations

Citations issued on November 18, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (November 24, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 23, 2025)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (November 24, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 30, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 30, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (January 30, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (November 24, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 23, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 24, 2025)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (November 24, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (November 24, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 23, 2025)

January 8, 2025 — 1 citation

Citations issued on January 8, 2025
TagWhat the surveyor checksStatus
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (February 28, 2025)

October 31, 2024 — 11 citations

Citations issued on October 31, 2024
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 26, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (December 26, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (December 26, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 26, 2024)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (December 26, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 26, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 26, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 26, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (December 26, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (December 26, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (December 26, 2024)

September 20, 2024 — 1 citation

Citations issued on September 20, 2024
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 15, 2024)

September 19, 2024 — 4 citations

Citations issued on September 19, 2024
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 15, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 15, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 15, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 15, 2024)

November 2, 2023 — 8 citations

Citations issued on November 2, 2023
TagWhat the surveyor checksStatus
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has date of correction (December 29, 2023)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 29, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (December 29, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (December 29, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 29, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 29, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (December 29, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 29, 2023)