Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

QUALITY LIFE SERVICES - MERCER

MERCER, PA · 48 certified beds · Last Life Safety survey June 18, 2026

CMS Certification Number 395879 · first certified September 1992

Ownership

Operated by QUALITY LIFE SERVICES · For profit - Partnership

  • Ownership changed September 1, 2024 (change of ownership)from COUNTRYSIDE CONVALESCENT HOME LIMITED PARTNERSHIP
15
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within PA

15 citations — more than 69% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 4.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens April 2027 — about 7 months from now. This facility’s last Life Safety survey was June 2026. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about QUALITY LIFE SERVICES - MERCER

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 15 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility15PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility15
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
42024-0752025-0662026-06
Citations at each Life Safety survey
Survey dateCitations
July 26, 20244
June 18, 20255
June 18, 20266

Most-cited tags

Most-cited tags at this facility
K-03453K-02912K-09181K-05211K-01331K-01001K-09121K-02231
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32026-06-18
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-06-18
K-0918Have generator or other power source capable of supplying service within 10 seconds.12024-07-26
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.12026-06-18
K-0133Install a two-hour-resistant firewall separation.12024-07-26
K-0100Meet other general requirements.12026-06-18
K-0912Have power receptacles that are properly grounded.12025-06-18
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.12026-06-18

What the citations cover

Citations by CMS category
  • Egress Deficiencies 4
  • Smoke Deficiencies 3
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
  • Construction Deficiencies 2
  • Other 3
Citations by CMS category
CategoryCitations
Egress Deficiencies4
Smoke Deficiencies3
Gas, Vacuum, and Electrical Systems Deficiencies3
Construction Deficiencies2
Miscellaneous Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 18, 2026 — 6 citations

Citations issued on June 18, 2026
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has plan of correction (July 31, 2026)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has plan of correction (July 31, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has plan of correction (July 31, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has plan of correction (July 31, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has plan of correction (July 31, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has plan of correction (July 31, 2026)

June 18, 2025 — 5 citations

Citations issued on June 18, 2025
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 7, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 7, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 7, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 7, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (August 7, 2025)

July 26, 2024 — 4 citations

Citations issued on July 26, 2024
TagWhat the surveyor checksStatus
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (September 2, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 2, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 2, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 2, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.