Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PARK LANE POST ACUTE LLC

WEST CHESTER, PA · 68 certified beds · Last Life Safety survey May 16, 2025

CMS Certification Number 396082 · first certified November 2002

Ownership

Operated by PRESTIGE HEALTHCARE ADMINISTRATIVE SERVICES · For profit - Corporation

  • Ownership changed June 17, 2024 (change of ownership)from WATERMARK PARK LANE, LLC
30
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
9
Tags cited more than once
Across separate surveys
13
Inspection & testing records
Of the citations on file

Position within PA

30 citations — more than 95% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 8 citations; the earlier surveys in the window averaged 11. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (March 2026 to May 2026), and past the point by which nine in ten PA facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PARK LANE POST ACUTE LLC

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 30 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 30 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility30PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility30
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
72023-06152024-0482025-05
Citations at each Life Safety survey
Survey dateCitations
June 23, 20237
April 19, 202415
May 16, 20258

Most-cited tags

Most-cited tags at this facility
K-01003K-03242K-09182K-03212K-03552K-02912K-02252K-09142
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0100Meet other general requirements.32025-05-16
K-0324Provide properly protected cooking facilities.22025-05-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-04-19
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22025-05-16
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-05-16
K-0291Install emergency lighting that can last at least 1 1/2 hours.22024-04-19
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.22024-04-19
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22024-04-19

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Egress Deficiencies 5
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Construction Deficiencies 4
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Egress Deficiencies5
Gas, Vacuum, and Electrical Systems Deficiencies5
Construction Deficiencies4
Miscellaneous Deficiencies3
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 16, 2025 — 8 citations

Citations issued on May 16, 2025
TagWhat the surveyor checksStatus
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (May 15, 2025)
K-0100Meet other general requirements.Deficient, Provider has date of correction (June 15, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 15, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 15, 2025)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (May 15, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 15, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 15, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 15, 2025)

April 19, 2024 — 15 citations

Citations issued on April 19, 2024
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (May 30, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (May 30, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 30, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (May 30, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 30, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 30, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 30, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 30, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 30, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 30, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 30, 2024)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (May 30, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (May 30, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (May 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 30, 2024)

June 23, 2023 — 7 citations

Citations issued on June 23, 2023
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (August 6, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (August 6, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 6, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 6, 2023)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (August 6, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 6, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 6, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.