Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

MT PLEASANT HEALTHCARE AND REHABILITATION

MOUNT PLEASANT, TN · 72 certified beds · Last Life Safety survey March 28, 2025

CMS Certification Number 445374 · first certified June 1996

Ownership

Operated by SIMCHA HYMAN & NAFTALI ZANZIPER · For profit - Limited Liability company

  • Ownership changed December 1, 2019 (change of ownership)to MT PLEASANT HEALTH AND REHABILITATION from HIDDEN ACRES HEALTHCARE, LLC
42
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within TN

42 citations — more than 100% of the 303 certified nursing homes in TN. Compared within TN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 2 citations; the earlier surveys in the window averaged 13.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: June 2026 to December 2028. This facility’s last Life Safety survey was March 2025. Facilities in TN are typically surveyed 15–44 months after the last one (median 33), measured over 279 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about MT PLEASANT HEALTHCARE AND REHABILITATION

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 42 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 42 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in TN, and nationally. Surveyors differ markedly between states, so the TN figure is the meaningful one.

This facility42TN median8National median11
Citations on file over three years, compared
MeasureCitations
This facility42
Median facility in TN8
Median facility nationally11

Survey history

Citations at each Life Safety survey
152019-0292019-12162025-0322025-03
Citations at each Life Safety survey
Survey dateCitations
February 12, 201915
December 18, 20199
March 20, 202516
March 28, 20252

Most-cited tags

Most-cited tags at this facility
K-03453K-05113K-03533E-00152K-05212K-03242K-09212K-02222
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-03-20
K-0511Have properly installed electrical wiring and gas equipment.32025-03-20
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-03-20
E-0015Address subsistence needs for staff and patients.22019-12-18
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22025-03-20
K-0324Provide properly protected cooking facilities.22019-12-18
K-0921Ensure that testing and maintenance of electrical equipment is performed.22025-03-28
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-03-20

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Emergency Preparedness Deficiencies 7
  • Egress Deficiencies 6
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies7
Emergency Preparedness Deficiencies7
Egress Deficiencies6
Services Deficiencies5
Miscellaneous Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 28, 2025 — 2 citations

Citations issued on March 28, 2025
TagWhat the surveyor checksStatus
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (April 14, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (April 14, 2025)

March 20, 2025 — 16 citations

Citations issued on March 20, 2025
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 28, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 28, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (April 28, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 28, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 28, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 28, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 28, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 28, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 28, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 28, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 28, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (April 28, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 28, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 28, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (April 28, 2025)
K-0929Ensure precautions for handling oxygen cylinders and equipment are correctly followed.Deficient, Provider has date of correction (April 28, 2025)

December 18, 2019 — 9 citations

Citations issued on December 18, 2019
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (January 31, 2020)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (January 31, 2020)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 31, 2020)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (January 31, 2020)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 31, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 31, 2020)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 31, 2020)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 31, 2020)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 31, 2020)

February 12, 2019 — 15 citations

Citations issued on February 12, 2019
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (March 28, 2019)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (March 28, 2019)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (March 28, 2019)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (March 28, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 12, 2019)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 11, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 25, 2019)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 18, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 11, 2019)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 11, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 28, 2019)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 28, 2019)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (May 11, 2019)
K-0751Have restrictions on the use of flammable curtains.Deficient, Provider has date of correction (March 28, 2019)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 28, 2019)