Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
Alpine Meadow Rehabilitation and Nursing
West Valley City, UT · 42 certified beds · Last Life Safety survey April 22, 2026
CMS Certification Number 465191 · first certified December 2019
Ownership
Operated by BEAVER VALLEY HOSPITAL · Government - City/county
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within UT
14 citations — more than 83% of the 97 certified nursing homes in UT. Compared within UT rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 2 citations; the earlier surveys in the window averaged 6. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2027 — about 14 months from now. This facility’s last Life Safety survey was April 2026. Facilities in UT are typically surveyed 19–24 months after the last one (median 21), measured over 88 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about Alpine Meadow Rehabilitation and Nursing
One email when it happens. No account; stop it any time with one click.
1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
3 of the 14 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 14 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in UT, and nationally. Surveyors differ markedly between states, so the UT figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 14 |
| Median facility in UT | 3 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| December 21, 2023 | 8 |
| April 3, 2025 | 4 |
| April 22, 2026 | 2 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2025-04-03 |
| E-0039 | Conduct testing and exercise requirements. | 2 | 2026-04-22 |
| K-0712 | Have simulated fire drills held at unexpected times. | 1 | 2023-12-21 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 1 | 2023-12-21 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 1 | 2025-04-03 |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 1 | 2023-12-21 |
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | 1 | 2026-04-22 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 1 | 2023-12-21 |
What the citations cover
- Smoke Deficiencies 4
- Gas, Vacuum, and Electrical Systems Deficiencies 4
- Emergency Preparedness Deficiencies 3
- Egress Deficiencies 1
- Other 2
| Category | Citations |
|---|---|
| Smoke Deficiencies | 4 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 4 |
| Emergency Preparedness Deficiencies | 3 |
| Egress Deficiencies | 1 |
| Services Deficiencies | 1 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 22, 2026 — 2 citations
April 3, 2025 — 4 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (April 24, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (April 24, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (April 24, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (April 24, 2025) |
December 21, 2023 — 8 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (December 26, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (December 27, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (December 27, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (December 27, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (December 27, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (December 27, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (December 27, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (December 27, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.