Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Ridgeview Terrace Long Term Care

Reedsburg, WI · 25 certified beds · Last Life Safety survey July 9, 2026

CMS Certification Number 525667 · first certified March 2003

Also on this campus

The same campus holds a state-licensed assisted living facilities, with their own state records on the Assisted Living Index: Ridgeview Place (2350 North Dewey Ave) and Ridgeview Trails (2350 North Dewey Avenue). Matched by the telephone number the two records share. The records are separate and are never added together.

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

11
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
1
Tags cited more than once
Across separate surveys
4
Inspection & testing records
Of the citations on file

Position within WI

11 citations — more than 21% of the 323 certified nursing homes in WI. Compared within WI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 1 citation; the earlier surveys on file averaged 5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens August 2027 — about 9 months from now. This facility’s last Life Safety survey was July 2026. Facilities in WI are typically surveyed 13–15 months after the last one (median 14), measured over 519 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about Ridgeview Terrace Long Term Care

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

How that compares

Citations in CMS's current file

Compared with the median facility in WI, and nationally. Surveyors differ markedly between states, so the WI figure is the meaningful one.

This facility11WI median17National median11
Citations in CMS's current file, compared
MeasureCitations
This facility11
Median facility in WI17
Median facility nationally11

Survey history

Citations at each Life Safety survey
62024-0542025-0412026-07
Citations at each Life Safety survey
Survey dateCitations
May 15, 20246
April 16, 20254
July 9, 20261

Most-cited tags

Most-cited tags at this facility
K-03722K-01321K-03531K-05411K-03621K-02231K-09201K-07121
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22025-04-16
K-0132Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.12024-05-15
K-0353Inspect, test, and maintain automatic sprinkler systems.12024-05-15
K-0541Install properly constructed and protected linen or trash chutes.12025-04-16
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.12024-05-15
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.12024-05-15
K-0920Ensure proper usage of power strips and extension cords.12025-04-16
K-0712Have simulated fire drills held at unexpected times.12025-04-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 5
  • Egress Deficiencies 2
  • Services Deficiencies 1
  • Gas, Vacuum, and Electrical Systems Deficiencies 1
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies5
Egress Deficiencies2
Services Deficiencies1
Gas, Vacuum, and Electrical Systems Deficiencies1
Miscellaneous Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 9, 2026 — 1 citation

Citations issued on July 9, 2026
TagWhat the surveyor checksStatus
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (August 3, 2026)

April 16, 2025 — 4 citations

Citations issued on April 16, 2025
TagWhat the surveyor checksStatus
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 2, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (May 2, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 2, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 2, 2025)

May 15, 2024 — 6 citations

Citations issued on May 15, 2024
TagWhat the surveyor checksStatus
K-0132Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.Waiver has been granted (November 8, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 30, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 30, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 30, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (June 30, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 30, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.