LIFE CARE CENTER OF TUCSON
TUCSON, AZ · 162 certified beds · Last Life Safety survey July 17, 2024
CMS Certification Number 035140 · first certified January 1987
Ownership
Operated by LIFE CARE CENTERS OF AMERICA · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within AZ
34 citations — more than 96% of the 140 certified nursing homes in AZ. Compared within AZ rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 18 citations; the earlier surveys in the window averaged 8. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (September 2025 to May 2026), and past the point by which nine in ten AZ facilities have been surveyed. This facility’s last Life Safety survey was July 2024. Facilities in AZ are typically surveyed 14–22 months after the last one (median 18), measured over 143 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about LIFE CARE CENTER OF TUCSON
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
10 of the 34 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 34 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0906 Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
How that compares
Compared with the median facility in AZ, and nationally. Surveyors differ markedly between states, so the AZ figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 34 |
| Median facility in AZ | 8 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 8, 2022 | 6 |
| March 14, 2023 | 10 |
| July 17, 2024 | 18 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0920 | Ensure proper usage of power strips and extension cords. | 3 | 2024-07-17 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2024-07-17 |
| E-0020 | Establish policies and procedures including evacuation. | 2 | 2024-07-17 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2024-07-17 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2024-07-17 |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 2 | 2023-03-14 |
| K-0915 | Have proper power supply for life support equipment. | 2 | 2024-07-17 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2024-07-17 |
What the citations cover
- Emergency Preparedness Deficiencies 10
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Smoke Deficiencies 8
- Egress Deficiencies 3
- Other 4
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 10 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Smoke Deficiencies | 8 |
| Egress Deficiencies | 3 |
| Services Deficiencies | 2 |
| Miscellaneous Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
July 17, 2024 — 18 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (August 23, 2024) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (August 23, 2024) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (August 23, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (November 18, 2024) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (August 23, 2024) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (August 23, 2024) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (August 23, 2024) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (November 18, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0915 | Have proper power supply for life support equipment. | Deficient, Provider has date of correction (November 18, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (November 18, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (August 23, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (August 23, 2024) |
March 14, 2023 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (May 12, 2023) |
| K-0200 | Meet other general requirements. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0915 | Have proper power supply for life support equipment. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (May 12, 2023) |
March 8, 2022 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (April 4, 2022) |
| K-0325 | Have properly installed hallway dispensers for alcohol-based hand rub. | Deficient, Provider has date of correction (April 4, 2022) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 4, 2022) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (April 4, 2022) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (April 4, 2022) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (April 4, 2022) |