Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
ALAMEDA HEALTHCARE & WELLNESS CENTER
ALAMEDA, CA · 166 certified beds · Last Life Safety survey August 10, 2024
CMS Certification Number 555486 · first certified November 1991
Ownership
Operated by SOL HEALTHCARE · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within CA
41 citations — more than 97% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 11 citations; the earlier surveys in the window averaged 7.5. With 5 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Past the typical window (August 2025 to January 2026). Most CA facilities have been surveyed by January 2027. This facility’s last Life Safety survey was August 2024. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about ALAMEDA HEALTHCARE & WELLNESS CENTER
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
2 of the 41 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0908 Keep all essential equipment working safely.
How that compares
Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 41 |
| Median facility in CA | 19 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| August 31, 2018 | 3 |
| July 19, 2019 | 13 |
| February 26, 2024 | 1 |
| March 18, 2024 | 13 |
| August 10, 2024 | 11 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0363 | Install corridor and hallway doors that block smoke. | 4 | 2024-08-10 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2024-08-10 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 3 | 2024-08-10 |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | 3 | 2024-08-10 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2024-08-10 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 2 | 2024-03-18 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2 | 2024-08-10 |
| K-0919 | Meet requirements for the use of electrical equipment. | 2 | 2024-08-10 |
What the citations cover
- Smoke Deficiencies 17
- Gas, Vacuum, and Electrical Systems Deficiencies 10
- Services Deficiencies 5
- Egress Deficiencies 4
- Other 5
| Category | Citations |
|---|---|
| Smoke Deficiencies | 17 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 10 |
| Services Deficiencies | 5 |
| Egress Deficiencies | 4 |
| Construction Deficiencies | 2 |
| Emergency Preparedness Deficiencies | 2 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
August 10, 2024 — 11 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (August 26, 2024) |
March 18, 2024 — 13 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (April 18, 2024) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (April 18, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (April 18, 2024) |
February 26, 2024 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (March 19, 2024) |
July 19, 2019 — 13 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (October 8, 2019) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (October 8, 2019) |
August 31, 2018 — 3 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (December 26, 2018) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (December 26, 2018) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (December 26, 2018) |