Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PIONEERS MEMORIAL SKILLED NURSING CENTER

BRAWLEY, CA · 99 certified beds · Last Life Safety survey January 10, 2025

CMS Certification Number 555557 · first certified June 1993

Ownership

Operated by CORPORATE INTERFACE SERVICES · Government - Hospital district

  • New ownershipOwnership changed January 21, 2025 (change of ownership)to PIONEERS MEMORIAL SKILLED NURSING FACILITY from PIONEERS MEMORIAL HEALTHCARE DISTRICT
34
Citations on file
Rolling three-year window
5
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within CA

34 citations — more than 90% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 5.5. With 5 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (January 2026 to July 2026). Most CA facilities have been surveyed by June 2027. This facility’s last Life Safety survey was January 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PIONEERS MEMORIAL SKILLED NURSING CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

5 of the 34 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 34 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility34CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility34
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
62022-1242023-0832023-0992024-02122025-01
Citations at each Life Safety survey
Survey dateCitations
December 15, 20226
August 18, 20234
September 6, 20233
February 20, 20249
January 10, 202512

Most-cited tags

Most-cited tags at this facility
K-07123K-03453K-09232K-09182K-03242K-03532K-01612K-03631
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32025-01-10
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-01-10
K-0923Have proper medical gas storage and administration areas.22024-02-20
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-01-10
K-0324Provide properly protected cooking facilities.22025-01-10
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-01-10
K-0161Use approved construction type or materials.22025-01-10
K-0363Install corridor and hallway doors that block smoke.12022-12-15

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Miscellaneous Deficiencies 5
  • Emergency Preparedness Deficiencies 5
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies7
Miscellaneous Deficiencies5
Emergency Preparedness Deficiencies5
Construction Deficiencies2
Egress Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 10, 2025 — 12 citations

Citations issued on January 10, 2025
TagWhat the surveyor checksStatus
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (January 22, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (January 16, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 16, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 16, 2025)
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.Deficient, Provider has date of correction (January 30, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 23, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 23, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 23, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 23, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 21, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (January 31, 2025)
K-0932Meet other general requirements.Deficient, Provider has date of correction (January 27, 2025)

February 20, 2024 — 9 citations

Citations issued on February 20, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (March 4, 2024)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (March 4, 2024)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (March 4, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 4, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 4, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 4, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (March 4, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 4, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 4, 2024)

September 6, 2023 — 3 citations

Citations issued on September 6, 2023
TagWhat the surveyor checksStatus
K-0200Meet other general requirements.Deficient, Provider has date of correction (September 26, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 26, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 26, 2023)

August 18, 2023 — 4 citations

Citations issued on August 18, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (September 25, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (September 25, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (September 25, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 25, 2023)

December 15, 2022 — 6 citations

Citations issued on December 15, 2022
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (January 12, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 12, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 12, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 12, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 12, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 12, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.