Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
CORONA HEALTH CARE CENTER
CORONA, CA · 99 certified beds · Last Life Safety survey July 24, 2025
CMS Certification Number 055255 · first certified December 1971
Also on this campus
The same campus holds a state-licensed assisted living facility, with its own state record on the Assisted Living Index: Corona Residential Care Center LLC (1400 Circle City Dr). Matched by the telephone number the two records share. The records are separate and are never added together.
Ownership
Independently operated (no chain recorded by CMS) · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within CA
29 citations — more than 82% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 8 citations; the earlier surveys in the window averaged 10.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: July 2026 to January 2027. This facility’s last Life Safety survey was July 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about CORONA HEALTH CARE CENTER
One email when it happens. No account; stop it any time with one click.
3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
7 of the 29 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 29 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
How that compares
Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 29 |
| Median facility in CA | 19 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 11, 2022 | 5 |
| June 28, 2024 | 16 |
| July 24, 2025 | 8 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0363 | Install corridor and hallway doors that block smoke. | 2 | 2025-07-24 |
| E-0031 | Provide emergency officials' contact information. | 2 | 2024-06-28 |
| E-0041 | Implement emergency and standby power systems. | 2 | 2025-07-24 |
| K-0324 | Provide properly protected cooking facilities. | 2 | 2025-07-24 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 2 | 2024-06-28 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2025-07-24 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 1 | 2024-06-28 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 1 | 2024-06-28 |
What the citations cover
- Smoke Deficiencies 9
- Emergency Preparedness Deficiencies 7
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Miscellaneous Deficiencies 3
- Other 4
| Category | Citations |
|---|---|
| Smoke Deficiencies | 9 |
| Emergency Preparedness Deficiencies | 7 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Miscellaneous Deficiencies | 3 |
| Egress Deficiencies | 2 |
| Construction Deficiencies | 1 |
| Services Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
July 24, 2025 — 8 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (August 7, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (August 7, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 7, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 7, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 7, 2025) |
| K-0917 | Ensure electrical receptacles or cover plates have distinctive color or marking. | Deficient, Provider has date of correction (August 7, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 21, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (August 7, 2025) |
June 28, 2024 — 16 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (July 31, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (July 31, 2024) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (July 31, 2024) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0325 | Have properly installed hallway dispensers for alcohol-based hand rub. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (July 31, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 31, 2024) |
March 11, 2022 — 5 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (April 5, 2022) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (April 5, 2022) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (April 5, 2022) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (April 5, 2022) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (April 5, 2022) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.