Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

THE ROWLAND

COVINA, CA · 126 certified beds · Last Life Safety survey May 16, 2025

CMS Certification Number 056117 · first certified January 1980

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

32
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within CA

32 citations — more than 88% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 13 citations; the earlier surveys in the window averaged 9.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: May 2026 to November 2026. This facility’s last Life Safety survey was May 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about THE ROWLAND

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 32 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 32 Life Safety citations above. The Physical Environment Index

  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility32CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility32
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
82021-06112024-06132025-05
Citations at each Life Safety survey
Survey dateCitations
June 11, 20218
June 10, 202411
May 16, 202513

Most-cited tags

Most-cited tags at this facility
K-03213K-09203K-03533E-00412K-03452K-09182K-03552K-02912
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-05-16
K-0920Ensure proper usage of power strips and extension cords.32025-05-16
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-05-16
E-0041Implement emergency and standby power systems.22025-05-16
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-05-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-05-16
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-05-16
K-0291Install emergency lighting that can last at least 1 1/2 hours.22024-06-10

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Miscellaneous Deficiencies 5
  • Emergency Preparedness Deficiencies 3
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies5
Emergency Preparedness Deficiencies3
Egress Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 16, 2025 — 13 citations

Citations issued on May 16, 2025
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 2, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (June 9, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 6, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 9, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (May 14, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 16, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 6, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 6, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 6, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 6, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 13, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 7, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 5, 2025)

June 10, 2024 — 11 citations

Citations issued on June 10, 2024
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (July 10, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 8, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 30, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 8, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 5, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 8, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 12, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 12, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 12, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 10, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 12, 2024)

June 11, 2021 — 8 citations

Citations issued on June 11, 2021
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 22, 2021)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 22, 2021)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (July 22, 2021)
K-0352Properly install and monitor supervisory attachments on automatic sprinkler systems.Deficient, Provider has date of correction (July 22, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 22, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 22, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 22, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 22, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.