Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

RIVERSIDE VILLAGE HEALTHCARE CENTER

RIVERSIDE, CA · 59 certified beds · Last Life Safety survey May 2, 2025

CMS Certification Number 555404 · first certified January 1990

Ownership

Operated by BVHC, LLC · For profit - Limited Liability company

  • Ownership changed September 4, 2019 (change of ownership)from AIR FORCE VILLAGE WEST, INC.
44
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within CA

44 citations — more than 98% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 19. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: May 2026 to October 2026. This facility’s last Life Safety survey was May 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about RIVERSIDE VILLAGE HEALTHCARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

10 of the 44 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

10 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0908 Keep all essential equipment working safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility44CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility44
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
222021-06162024-0562025-05
Citations at each Life Safety survey
Survey dateCitations
June 25, 202122
May 9, 202416
May 2, 20256

Most-cited tags

Most-cited tags at this facility
K-03453K-03533K-09183K-03633K-07412E-00312K-01612K-07612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-05-02
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-05-02
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-05-02
K-0363Install corridor and hallway doors that block smoke.32025-05-02
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22025-05-02
E-0031Provide emergency officials' contact information.22024-05-09
K-0161Use approved construction type or materials.22024-05-09
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22025-05-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Emergency Preparedness Deficiencies 10
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Miscellaneous Deficiencies 5
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Emergency Preparedness Deficiencies10
Gas, Vacuum, and Electrical Systems Deficiencies9
Miscellaneous Deficiencies5
Egress Deficiencies4
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 2, 2025 — 6 citations

Citations issued on May 2, 2025
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 30, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 6, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 6, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 6, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 6, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 6, 2025)

May 9, 2024 — 16 citations

Citations issued on May 9, 2024
TagWhat the surveyor checksStatus
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (June 13, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (June 13, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (June 13, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (June 13, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 13, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 13, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 13, 2024)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (June 13, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 13, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 13, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 13, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (June 13, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 13, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 13, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 13, 2024)
K-0928Ensure equipment listed for use in oxygen-enriched atmospheres are correctly labeled.Deficient, Provider has date of correction (June 13, 2024)

June 25, 2021 — 22 citations

Citations issued on June 25, 2021
TagWhat the surveyor checksStatus
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (August 11, 2021)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (August 11, 2021)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (August 11, 2021)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (August 11, 2021)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (August 11, 2021)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (August 11, 2021)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 11, 2021)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (August 11, 2021)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 11, 2021)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 11, 2021)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 11, 2021)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 11, 2021)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (August 11, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 11, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 11, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 11, 2021)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 11, 2021)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 11, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 11, 2021)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (August 11, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 11, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 11, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.