Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

McKinley Park Care Center

Sacramento, CA · 86 certified beds · Last Life Safety survey January 23, 2026

CMS Certification Number 555122 · first certified December 1979

Ownership

Operated by PACS GROUP · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

46
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within CA

46 citations — more than 98% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 16. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was January 2026. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about McKinley Park Care Center

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

8 of the 46 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 46 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility46CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility46
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
192022-11132024-10142026-01
Citations at each Life Safety survey
Survey dateCitations
November 4, 202219
October 4, 202413
January 23, 202614

Most-cited tags

Most-cited tags at this facility
K-03633K-03533K-03553K-03423K-07123E-00393E-00232K-03212
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.32026-01-23
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-01-23
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.32026-01-23
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.32026-01-23
K-0712Have simulated fire drills held at unexpected times.32026-01-23
E-0039Conduct testing and exercise requirements.32026-01-23
E-0023Establish policies and procedures for medical documentation.22026-01-23
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22026-01-23

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 20
  • Emergency Preparedness Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Egress Deficiencies 5
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies20
Emergency Preparedness Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies6
Egress Deficiencies5
Miscellaneous Deficiencies4
Services Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 23, 2026 — 14 citations

Citations issued on January 23, 2026
TagWhat the surveyor checksStatus
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (February 13, 2026)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (March 5, 2026)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (February 17, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 13, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 17, 2026)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (February 17, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 13, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (February 13, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 13, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 18, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 13, 2026)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (February 13, 2026)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (March 18, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 18, 2026)

October 4, 2024 — 13 citations

Citations issued on October 4, 2024
TagWhat the surveyor checksStatus
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (October 21, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 21, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 21, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 21, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 21, 2024)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (October 21, 2024)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (October 21, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 21, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 21, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 21, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 21, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 21, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 21, 2024)

November 4, 2022 — 19 citations

Citations issued on November 4, 2022
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (December 13, 2022)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (December 13, 2022)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 13, 2022)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (December 13, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 13, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (December 13, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 13, 2022)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (December 13, 2022)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (December 13, 2022)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (December 13, 2022)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (December 13, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 13, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 13, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 13, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (December 13, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 13, 2022)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (December 13, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 13, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (December 13, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.