Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

THE PAVILION AT OCEAN POINT

SAN DIEGO, CA · 133 certified beds · Last Life Safety survey March 2, 2026

CMS Certification Number 055322 · first certified December 1969

Ownership

Operated by PACIFIC HEALTHCARE HOLDINGS · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

38
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within CA

38 citations — more than 95% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 8.7. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 5 months from now. This facility’s last Life Safety survey was March 2026. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about THE PAVILION AT OCEAN POINT

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

5 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility38CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
62023-10192024-1012025-07122026-03
Citations at each Life Safety survey
Survey dateCitations
October 26, 20236
October 24, 202419
July 24, 20251
March 2, 202612

Most-cited tags

Most-cited tags at this facility
K-09184K-05212K-09202E-00412K-07412K-07532K-03452K-07122
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.42026-03-02
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22024-10-24
K-0920Ensure proper usage of power strips and extension cords.22026-03-02
E-0041Implement emergency and standby power systems.22026-03-02
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22024-10-24
K-0753Have restrictions on the use of highly flammable decorations.22026-03-02
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22026-03-02
K-0712Have simulated fire drills held at unexpected times.22026-03-02

What the citations cover

Citations by CMS category
  • Gas, Vacuum, and Electrical Systems Deficiencies 12
  • Smoke Deficiencies 9
  • Miscellaneous Deficiencies 6
  • Emergency Preparedness Deficiencies 5
  • Other 6
Citations by CMS category
CategoryCitations
Gas, Vacuum, and Electrical Systems Deficiencies12
Smoke Deficiencies9
Miscellaneous Deficiencies6
Emergency Preparedness Deficiencies5
Egress Deficiencies3
Services Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 2, 2026 — 12 citations

Citations issued on March 2, 2026
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (March 26, 2026)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (March 26, 2026)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (March 26, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 26, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 7, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 26, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 26, 2026)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (March 26, 2026)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (March 26, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 26, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 26, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 26, 2026)

July 24, 2025 — 1 citation

Citations issued on July 24, 2025
TagWhat the surveyor checksStatus
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 11, 2025)

October 24, 2024 — 19 citations

Citations issued on October 24, 2024
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (November 26, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (November 26, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (November 26, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 26, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (November 26, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 26, 2024)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (November 26, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 26, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 26, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (November 26, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 26, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 26, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (November 26, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 26, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 26, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (November 26, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 26, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (November 26, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 26, 2024)

October 26, 2023 — 6 citations

Citations issued on October 26, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (November 17, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 17, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (November 17, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (November 17, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 17, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 17, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.