Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

LAGUNA HONDA HOSPITAL & REHABILITATION CTR D/P SNF

SAN FRANCISCO, CA · 769 certified beds · Last Life Safety survey August 19, 2026

CMS Certification Number 555929 · first certified May 2024

Ownership

Independently operated (no chain recorded by CMS) · For profit - Individual

No change of ownership on CMS record since January 1, 2016, when the records begin.

One or more citations below are marked by CMS as under Informal Dispute Resolution.
35
Citations on file
CMS's current file
11
Life Safety surveys
CMS's current file
7
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within CA

35 citations — more than 92% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 1 citation; the earlier surveys on file averaged 3.4. With 11 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens August 2027 — about 9 months from now. This facility’s last Life Safety survey was August 2026. Facilities in CA are typically surveyed 12–16 months after the last one (median 14), measured over 1,814 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about LAGUNA HONDA HOSPITAL & REHABILITATION CTR D/P SNF

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 35 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations in CMS's current file

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility35CA median19National median11
Citations in CMS's current file, compared
MeasureCitations
This facility35
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
92024-11112025-0512025-0812025-1222026-0312026-0412026-0612026-0662026-0712026-0812026-08
Citations at each Life Safety survey
Survey dateCitations
November 8, 20249
May 2, 202511
August 5, 20251
December 11, 20251
March 4, 20262
April 16, 20261
June 8, 20261
June 23, 20261
July 17, 20266
August 13, 20261
August 19, 20261

Most-cited tags

Most-cited tags at this facility
K-03536K-03634K-09183K-03742K-05112K-05212K-09192K-07121
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.62026-07-17
K-0363Install corridor and hallway doors that block smoke.42026-08-19
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-07-17
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22025-05-02
K-0511Have properly installed electrical wiring and gas equipment.22025-05-02
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22026-06-23
K-0919Meet requirements for the use of electrical equipment.22026-07-17
K-0712Have simulated fire drills held at unexpected times.12025-05-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 17
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Services Deficiencies 4
  • Miscellaneous Deficiencies 4
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies17
Gas, Vacuum, and Electrical Systems Deficiencies7
Services Deficiencies4
Miscellaneous Deficiencies4
Egress Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 19, 2026 — 1 citation

Citations issued on August 19, 2026
TagWhat the surveyor checksStatus
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 1, 2026)

August 13, 2026 — 1 citation

Citations issued on August 13, 2026
TagWhat the surveyor checksStatus
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (September 1, 2026)

July 17, 2026 — 6 citations

Citations issued on July 17, 2026
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 13, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 14, 2026)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (August 1, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 13, 2026)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (August 1, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 1, 2026)

June 23, 2026 — 1 citation

Citations issued on June 23, 2026
TagWhat the surveyor checksStatus
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 10, 2026)

June 8, 2026 — 1 citation

Citations issued on June 8, 2026
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 30, 2026) · under dispute

April 16, 2026 — 1 citation

Citations issued on April 16, 2026
TagWhat the surveyor checksStatus
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (May 11, 2026)

March 4, 2026 — 2 citations

Citations issued on March 4, 2026
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 23, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 23, 2026)

December 11, 2025 — 1 citation

Citations issued on December 11, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 3, 2026)

August 5, 2025 — 1 citation

Citations issued on August 5, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 18, 2025)

May 2, 2025 — 11 citations

Citations issued on May 2, 2025
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (June 2, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (June 2, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 2, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 2, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 2, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 2, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 2, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 2, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 2, 2025)
K-0771Ensure that smoke control systems are tested and documented in accordance with established engineering principles.Deficient, Provider has date of correction (June 2, 2025)
K-0908Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.Deficient, Provider has date of correction (June 2, 2025)

November 8, 2024 — 9 citations

Citations issued on November 8, 2024
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 9, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 9, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 9, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 9, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (December 9, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 9, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (December 9, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 9, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (December 9, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.