Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WESTWOOD POST ACUTE

SAN JOSE, CA · 258 certified beds · Last Life Safety survey April 18, 2025

CMS Certification Number 055750 · first certified July 1978

Ownership

Operated by LINKS HEALTHCARE GROUP · For profit - Limited Liability company

  • Ownership changed October 7, 2019 (change of ownership)from WESTGATE PREMIER HEALTHCARE SERVICES, INC.
23
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
15
Inspection & testing records
Of the citations on file

Position within CA

23 citations — more than 63% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 8.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: April 2026 to October 2026. This facility’s last Life Safety survey was April 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about WESTWOOD POST ACUTE

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 23 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

10 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 23 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0908 Keep all essential equipment working safely.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility23CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility23
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
102021-0472023-1162025-04
Citations at each Life Safety survey
Survey dateCitations
April 26, 202110
November 21, 20237
April 18, 20256

Most-cited tags

Most-cited tags at this facility
K-03633K-03453K-09182K-09202K-01612E-00412K-03532K-02911
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.32025-04-18
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-04-18
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-04-18
K-0920Ensure proper usage of power strips and extension cords.22025-04-18
K-0161Use approved construction type or materials.22023-11-21
E-0041Implement emergency and standby power systems.22025-04-18
K-0353Inspect, test, and maintain automatic sprinkler systems.22023-11-21
K-0291Install emergency lighting that can last at least 1 1/2 hours.12021-04-26

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Emergency Preparedness Deficiencies 2
  • Construction Deficiencies 2
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Gas, Vacuum, and Electrical Systems Deficiencies6
Emergency Preparedness Deficiencies2
Construction Deficiencies2
Miscellaneous Deficiencies1
Egress Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 18, 2025 — 6 citations

Citations issued on April 18, 2025
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (May 10, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 10, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 10, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 10, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 6, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 10, 2025)

November 21, 2023 — 7 citations

Citations issued on November 21, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (January 22, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 22, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 22, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 22, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (January 22, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Waiver has been granted (January 22, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (January 22, 2024)

April 26, 2021 — 10 citations

Citations issued on April 26, 2021
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (June 10, 2021)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (June 10, 2021)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 10, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 10, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 10, 2021)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 10, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 10, 2021)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 10, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 10, 2021)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 10, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.