Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
SEAL BEACH HEALTH AND REHABILITATION CENTER
SEAL BEACH, CA · 198 certified beds · Last Life Safety survey April 22, 2025
CMS Certification Number 056010 · first certified December 1971
Ownership
Operated by CAMBRIDGE HEALTHCARE SERVICES · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within CA
35 citations — more than 92% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 6 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: April 2026 to October 2026. This facility’s last Life Safety survey was April 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about SEAL BEACH HEALTH AND REHABILITATION CENTER
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
13 of the 35 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
21 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 35 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0908 Keep all essential equipment working safely.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
How that compares
Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 35 |
| Median facility in CA | 19 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| May 12, 2021 | 22 |
| June 29, 2023 | 7 |
| April 22, 2025 | 6 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0363 | Install corridor and hallway doors that block smoke. | 3 | 2025-04-22 |
| E-0041 | Implement emergency and standby power systems. | 2 | 2025-04-22 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2025-04-22 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-04-22 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2023-06-29 |
| E-0009 | Include a process for Emergency Preparedness collaboration. | 1 | 2021-05-12 |
| K-0929 | Ensure precautions for handling oxygen cylinders and equipment are correctly followed. | 1 | 2021-05-12 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 1 | 2021-05-12 |
What the citations cover
- Emergency Preparedness Deficiencies 13
- Smoke Deficiencies 10
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Egress Deficiencies 3
- Other 3
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 13 |
| Smoke Deficiencies | 10 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Egress Deficiencies | 3 |
| Miscellaneous Deficiencies | 1 |
| Services Deficiencies | 1 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 22, 2025 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (April 29, 2025) |
June 29, 2023 — 7 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 13, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (July 13, 2023) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (July 13, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (July 13, 2023) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (July 13, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 13, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (July 13, 2023) |
May 12, 2021 — 22 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (June 24, 2021) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (June 24, 2021) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0917 | Ensure electrical receptacles or cover plates have distinctive color or marking. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (June 24, 2021) |
| K-0929 | Ensure precautions for handling oxygen cylinders and equipment are correctly followed. | Deficient, Provider has date of correction (June 24, 2021) |