Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
BROOKSIDE CARE CENTER
STOCKTON, CA · 99 certified beds · Last Life Safety survey May 13, 2026
CMS Certification Number 055304 · first certified January 1967
Ownership
Operated by AJC HEALTHCARE · For profit - Limited Liability company
- Ownership changed May 1, 2021 (change of ownership)from DYCORA TRANSITIONAL HEALTH QUAIL LAKE LLC
Position within CA
53 citations — more than 100% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 20 citations; the earlier surveys in the window averaged 8.3. With 5 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens May 2027 — about 8 months from now. This facility’s last Life Safety survey was May 2026. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about BROOKSIDE CARE CENTER
One email when it happens. No account; stop it any time with one click.
8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
9 of the 53 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
18 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 53 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0908 Keep all essential equipment working safely.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
How that compares
Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 53 |
| Median facility in CA | 19 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| January 16, 2024 | 17 |
| January 31, 2025 | 13 |
| February 7, 2025 | 1 |
| December 4, 2025 | 2 |
| May 13, 2026 | 20 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0324 | Provide properly protected cooking facilities. | 3 | 2026-05-13 |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 3 | 2026-05-13 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-05-13 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2026-05-13 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2026-05-13 |
| K-0919 | Meet requirements for the use of electrical equipment. | 3 | 2026-05-13 |
| K-0293 | Have properly located and lighted "Exit" signs. | 3 | 2026-05-13 |
| E-0039 | Conduct testing and exercise requirements. | 3 | 2026-05-13 |
What the citations cover
- Smoke Deficiencies 18
- Emergency Preparedness Deficiencies 9
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Miscellaneous Deficiencies 8
- Other 9
| Category | Citations |
|---|---|
| Smoke Deficiencies | 18 |
| Emergency Preparedness Deficiencies | 9 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Miscellaneous Deficiencies | 8 |
| Egress Deficiencies | 6 |
| Services Deficiencies | 3 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 13, 2026 — 20 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (June 15, 2026) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (June 15, 2026) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (June 15, 2026) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (June 15, 2026) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0522 | Have an externally vented heating system. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 15, 2026) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (June 15, 2026) |
December 4, 2025 — 2 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0522 | Have an externally vented heating system. | Deficient, Provider has date of correction (January 4, 2026) |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. | Deficient, Provider has date of correction (January 4, 2026) |
February 7, 2025 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (February 24, 2025) |
January 31, 2025 — 13 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (March 3, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (March 3, 2025) |
January 16, 2024 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (February 2, 2024) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (February 2, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (February 2, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (February 2, 2024) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.